Conduit Fill Calculator
Find conduit fill percentage or maximum THHN conductor count for common conduit types and sizes.
Turn2Engineering • Electrical Calculators
Conduit Fill Calculator
Use this calculator to check conduit fill percentage or find the maximum number of THHN/THWN-2 conductors allowed in EMT, PVC Schedule 40/80, or RMC/IMC. It follows National Electrical Code (NEC) Chapter 9 raceway fill rules so you can verify compliance before you pull wire.
Quick Start
Conduit fill checks prevent failed inspections and brutal wire pulls. The calculator is built around the NEC area method (Chapter 9) and is meant for fast, reliable decisions in both design and field planning. Follow these steps to get a correct answer the first time.
- 1 Choose Solve For: Conduit Fill Percentage if you already know how many conductors will be installed, or Maximum Conductors Allowed if the conduit size is fixed and you need the code maximum.
- 2 Select the Conduit Type (EMT, PVC Schedule 40, or RMC/IMC). Internal raceway area differs by material, so changing this selection often changes the result even at the same trade size.
- 3 Pick the Conduit Trade Size (e.g., ½″, ¾″, 1″, 2″). The calculator pulls the internal area \(A_c\) from NEC Chapter 9, Table 4.
- 4 Choose the Conductor Size for THHN/THWN-2. The calculator uses the approximate conductor area \(a_w\) from NEC Chapter 9, Table 5.
- 5 If solving for fill percentage, enter the Number of Conductors \(n\). Use a whole number and include every conductor inside the raceway (including grounds and neutrals).
-
6
Review the result and the Quick Stats. The calculator compares your fill to NEC limits:
- 1 conductor → 53% maximum fill
- 2 conductors → 31% maximum fill
- 3+ conductors → 40% maximum fill
- 7 Click Show Steps to see the exact lookup areas used and the equation substitution. This is useful for plan notes, inspection questions, and verifying mixed-size runs by hand.
Choosing Your Method
Engineers and electricians commonly verify conduit fill in three ways. The calculator implements the NEC area method, but understanding the alternatives helps you choose the right level of rigor for each job.
1) NEC Area Method (Recommended)
This is the formal code method. It calculates conductor area and conduit internal area in square inches and applies NEC fill limits based on conductor count.
- Direct NEC compliance
- Works for any conduit and wire size
- Transparent for plan review and inspection
- Requires correct tables
- Mixed sizes need manual summation
2) Pre-tabulated Fill Charts
Field and manufacturer charts give max conductor counts by raceway size. They’re fast, but only correct if the chart matches the exact conduit type and insulation.
- Very fast on site
- No math required
- Easy to use the wrong chart edition
- Doesn’t cover unusual combinations
3) “Pullability First” Design
Many designers cap practical fill below NEC (often 25–35%) for long runs or heavy conductors and then verify code second. This improves installability and reduces risk of damaging insulation.
- Reduces pulling tension and labor
- Better thermal behavior in tough installs
- May increase conduit size/cost
- Not needed for short/simple runs
In practice, method (1) is what you document for compliance. Method (3) is how you avoid a pull that turns into a change order. If you are within a few percent of the NEC limit, upsizing is usually the safer and cheaper choice.
What Moves the Number
Conduit fill is driven by a small set of levers. Knowing how each one affects the result helps you interpret outputs correctly and spot input mistakes.
Conductor count \(n\)
Total fill scales directly with conductor count. One added conductor increases fill by \(\dfrac{a_w}{A_c}\times 100\), which can be several percent in small conduits.
Conductor area \(a_w\)
Area rises quickly with wire size. For example, jumping from #12 to #8 AWG more than doubles \(a_w\), so fill can spike even if \(n\) is unchanged.
Conduit area \(A_c\)
Internal area depends on conduit type and trade size. A 1″ EMT and 1″ PVC have different internal diameters, so fill capacities differ.
NEC fill factor \(k\)
Allowable fill is 53% for one conductor, 31% for two, and 40% for three or more. That means a two-wire run can be more restrictive than a three-wire run, even though the third wire increases total area.
Wire insulation type
This calculator uses THHN/THWN-2 areas. If you’re using XHHW-2 or specialty cable, substitute their areas from the appropriate NEC table.
Mixed wire sizes
Mixed runs require summing areas. A few large conductors can dominate fill, so don’t assume the small conductors “don’t matter.”
Worked Examples
The examples below follow the same equations and NEC tables used by the calculator. Use them as templates for validation or for mixed-size manual checks.
Example 1 — Fill Percentage Check
- Conduit type: EMT
- Trade size: 1″
- Conductor size: 12 AWG THHN
- Conductor count: \(n=9\)
NEC areas: \(A_c=0.864\ \text{in}^2\) (1″ EMT), \(a_w=0.0133\ \text{in}^2\) (12 AWG THHN).
Total wire area: \[ A_{\text{total}} = n a_w = 9(0.0133) = 0.1197\ \text{in}^2 \]
Fill percentage: \[ \%Fill = \frac{A_{\text{total}}}{A_c}\times 100 =\frac{0.1197}{0.864}\times 100 = 13.9\% \]
NEC limit for 3+ conductors is 40%. Since \(13.9\%<40\%\), the run complies.
Example 2 — Maximum Conductors Allowed
- Conduit type: PVC Schedule 40
- Trade size: ¾″
- Conductor size: 6 AWG THHN
NEC areas: \(A_c=0.508\ \text{in}^2\) (¾″ PVC Sch 40), \(a_w=0.0507\ \text{in}^2\) (6 AWG THHN).
Allowable fill areas: \[ A_{\max,1}=0.53A_c=0.269\ \text{in}^2 \] \[ A_{\max,2}=0.31A_c=0.157\ \text{in}^2 \] \[ A_{\max,3+}=0.40A_c=0.203\ \text{in}^2 \]
Convert to counts: \[ n_{\max,1}=\left\lfloor \frac{0.269}{0.0507}\right\rfloor=5 \] \[ n_{\max,2}=\left\lfloor \frac{0.157}{0.0507}\right\rfloor=3 \] \[ n_{\max,3+}=\left\lfloor \frac{0.203}{0.0507}\right\rfloor=4 \]
The largest valid 3+ category result is \(n_{\max}=4\). The calculator returns 4 conductors allowed.
Common Layouts & Variations
Conduit fill shows up differently depending on the application. This table summarizes common real-world setups, the raceway types you’ll typically see, and what usually drives sizing decisions.
| Scenario | Typical Conduit | Typical Conductors | What controls? | Notes / Pros & Cons |
|---|---|---|---|---|
| Branch circuits in commercial interiors | EMT ¾″–1″ | #12–#10 THHN | Fill + pullability | EMT bends easily; a few extra circuits can push small sizes over 40%. |
| Underground feeder to transformer or inverter | PVC Sch 40/80 2″–4″ | 1/0–500 kcmil | Conductor size dominates | Sch 80 risers for physical protection; PVC internal area differs from EMT. |
| Exposed rooftop / industrial runs | RMC/IMC 1″+ | #8–#2 THHN | Mechanical protection | RMC/IMC is durable but heavier and slower to install. |
| Motor/control bundle in one raceway | EMT 1″–2″ | Mixed sizes | Mixed-area summation | Sum all conductor areas; grounds still count for fill. |
| Single large conductor pull | Any | 600–1000 kcmil | 53% rule + stiffness | 53% allowed, but pulling one huge conductor can still justify upsizing. |
| Two parallel feeders in one conduit | Any | Two large conductors | 31% rule | Two-conductor limit is strict; often forces a bigger raceway. |
Specs, Logistics & Sanity Checks
Before finalizing conduit size in drawings or pull schedules, run these practical checks. They make sure the calculator result is code-correct and buildable in the real world.
Confirm the wire type
- THHN/THWN-2 areas are assumed in this calculator.
- If using XHHW-2, RHW-2, MC cable, tray cable, or specialty conductors, use their NEC areas instead.
- Temperature rating affects ampacity, not fill, but is usually checked alongside fill.
Count conductors correctly
- Include all conductors in the raceway, including grounds and neutrals.
- For multi-circuit conduits, total everything inside the pipe.
- Don’t double-count parallel sets that are installed in separate conduits.
- For mixed sizes, sum areas first: \(A_{\text{total}}=\sum n_i a_{w,i}\).
Check pullability
- Long runs with multiple bends increase pulling tension dramatically.
- Near-limit fills in small conduits can be difficult even on short runs.
- Consider designing to 25–35% fill for tough pulls.
- Plan for lubricant, pulling heads, and box spacing.
Remember derating
- 3+ current-carrying conductors trigger ampacity adjustment factors (NEC 310).
- High ambient temperatures may require additional derating.
- Fill compliance does not guarantee thermal compliance.
