Power Factor Calculator

Calculate power factor, kVA, kVAR, phase angle, line current, and capacitor bank correction size for AC electrical systems.

Calculator is for informational purposes only. Terms and Conditions

\[ PF=\frac{P}{S} \]
1

Choose what to solve for

Select the AC power calculation, input method, phase type, and unit preset.

Choose the unknown value. The known-value inputs update automatically.
For power factor, choose the values you already know.
Three-phase calculations use line-to-line voltage by default.
Electrical default uses kW, kVA, kVAR, V, and A.
Enter real power and apparent power to calculate power factor.
2

Enter the known values

Only the fields needed for the selected power factor calculation are shown.

Real power is the useful power doing work, commonly measured in kW.
Apparent power combines real and reactive power and is commonly measured in kVA.
Reactive power is the non-working AC power associated with magnetic or electric fields.
Use a decimal such as 0.85 or a percent such as 85 depending on the selected format.
Typical correction targets are 0.90, 0.95, or 0.98. Avoid overcorrection without system review.
For three-phase systems, use line-to-line voltage unless line-to-neutral is selected in advanced options. In correction mode, voltage is optional and is used only to estimate current reduction.
Line current is used with voltage and power factor to calculate AC power.
Advanced Options
3

Visual Check

Use the power triangle to compare real, reactive, and apparent power.

Power factor power triangle visual A dynamic power triangle that updates with the calculated real power, reactive power, apparent power, and phase angle.
4

Solution

Live result, quick checks, warnings, and full solution steps.

Power Factor
PF
Real-time result updates as you type.

Quick checks

  • Phase angle
Show solution steps See the equation, substitutions, assumptions, and result path
  1. Enter values to see the full solution steps and checks.
5

Source, Standards, and Assumptions

Calculation basis, constants, assumptions, and limitations.

Standard AC power relationships

Uses standard sinusoidal AC power triangle relationships for educational estimating. Final electrical design must be verified against applicable codes, utility requirements, equipment ratings, manufacturer data, and qualified engineering judgment.

  • Assumptions will appear after a valid calculation.
On this page

Calculator Guide

How to Use the Power Factor Calculator

The Power Factor Calculator above helps calculate power factor from kW and kVA, kW and kVAR, or kW, voltage, and current. It can also help estimate apparent power, real power, reactive power, phase angle, line current, and power factor correction kVAR using the AC power triangle.

Power factor is the ratio of real power to apparent power, so the basic formula is \(PF=P/S\). After using the calculator, use the sections below to verify the formula, check your units, understand the result, and decide whether the value is reasonable for your system.

Best for kW/kVA, kW/kVAR, voltage-current, and correction kVAR calculations
Main result Power factor, phase angle, apparent power, reactive power, line current, or capacitor kVAR
Most important input Correct power units and the correct single-phase or three-phase voltage convention

Quick Answer

To calculate power factor from kW and kVA, use \(PF=P/S\). To calculate power factor from kW and kVAR, use \(PF=P/\sqrt{P^2+Q^2}\). For a balanced three-phase system using line-to-line voltage, calculate \(S=\sqrt{3}V_{LL}I/1000\), then calculate \(PF=P/S\). A power factor closer to 1.0 means a larger share of apparent power is being converted into useful real power.

Why power factor matters

Low power factor can increase line current, transformer loading, conductor losses, voltage drop, and utility demand charges. Improving power factor can reduce kVA demand, but it does not usually reduce the real power required by the load.

Do not rely on a simplified calculator when…

Do not use a simplified power factor calculation as the only basis for final capacitor bank design, harmonic filter selection, utility compliance, protection coordination, or nonlinear load analysis. Systems with VFDs, rectifiers, UPS equipment, switching capacitor banks, or high harmonic distortion need deeper power quality review.

Inputs and Outputs Used by the Calculator

A power factor calculation can start from several different known values. The most common inputs are real power, apparent power, reactive power, voltage, current, existing power factor, and target power factor.

Power Factor Calculator inputs and outputs
TypeValueWhat It MeansCommon Unit
InputReal Power, \(P\)Useful power converted into work, heat, light, motion, or other real output.W, kW, MW
InputApparent Power, \(S\)Total AC power demand based on RMS voltage and current.VA, kVA, MVA
InputReactive Power, \(Q\)Power exchanged between the source and reactive elements such as inductors and capacitors.VAR, kVAR, MVAR
InputVoltage, \(V\)RMS AC voltage used with current to calculate apparent power.V, kV
InputCurrent, \(I\)RMS line current. For three-phase systems, use line current.A, kA
InputExisting Power FactorCurrent or measured power factor before correction.decimal or percent
InputTarget Power FactorDesired corrected power factor used to estimate required capacitive kVAR.decimal or percent
OutputPower Factor, \(PF\)Ratio of real power to apparent power.decimal or percent
OutputPhase Angle, \(\phi\)Angle between voltage and current for displacement power factor.degrees
OutputCorrection \(Q_c\)Estimated capacitive reactive power required to improve lagging power factor.kVAR

Power Factor Formula

To calculate power factor manually, choose the formula that matches the values you know: kW and kVA, kW and kVAR, or kW with voltage and current. The calculator uses standard AC power triangle relationships and phase-specific apparent power formulas.

Power Factor Formula Cheat Sheet

Common power factor formulas by known values
Known ValuesFormulaUse Case
kW and kVA\(PF=P/S\)Direct power factor calculation
kW and kVAR\(PF=P/\sqrt{P^2+Q^2}\)Power triangle calculation
kW, V, and A single-phase\(S=VI/1000,\quad PF=P/S\)Single-phase field measurement check
kW, \(V_{LL}\), and A three-phase\(S=\sqrt{3}V_{LL}I/1000,\quad PF=P/S\)Three-phase line-to-line calculation
kW, \(PF_1\), and \(PF_2\)\(Q_c=P[\tan(\phi_1)-\tan(\phi_2)]\)Power factor correction kVAR estimate

Power Factor from kW and kVA

To calculate power factor from kW and kVA, divide real power by apparent power. For example, if a load uses \(80\,kW\) and draws \(100\,kVA\), the power factor is \(80/100=0.80\).

\[ PF=\frac{P}{S} \]

Use matching unit scales for \(P\) and \(S\). For example, use kW with kVA or W with VA.

Power Factor from kW and kVAR

To calculate power factor from kW and kVAR, first calculate apparent power from the power triangle, then divide real power by apparent power.

\[ S=\sqrt{P^2+Q^2} \]
\[ PF=\frac{P}{\sqrt{P^2+Q^2}} \]

Use matching unit scales for \(P\), \(S\), and \(Q\). For example, use kW with kVA and kVAR.

Single-Phase Power Factor from Voltage and Current

For a single-phase AC load, calculate apparent power with \(S=VI/1000\), then calculate \(PF=P/S\). This is useful when you know real power in kW, RMS voltage, and RMS current.

\[ S=\frac{VI}{1000} \]

Use voltage in volts and current in amps to get \(S\) in kVA. Use kW for \(P\) when calculating \(PF=P/S\).

Three-Phase Power Factor from Line-to-Line Voltage

For a balanced three-phase system using line-to-line voltage, calculate apparent power with the \(\sqrt{3}\) relationship, then divide real power by apparent power.

\[ S=\frac{\sqrt{3}V_{LL}I}{1000} \]

Use this form when the voltage input is measured phase-to-phase. For voltage-current calculations, use kW, voltage, and current measured at the same time and same load condition.

Three-Phase Power Factor from Line-to-Neutral Voltage

If the three-phase voltage input is line-to-neutral instead of line-to-line, use the \(3V_{LN}I\) form for apparent power.

\[ S=\frac{3V_{LN}I}{1000} \]

Do not mix this with line-to-line voltage. Using the wrong voltage convention is one of the most common reasons a three-phase power factor result is wrong.

Phase Angle and Power Factor

Power factor is also the cosine of the phase angle between voltage and current for displacement power factor. A smaller angle means a higher power factor.

\[ PF=\cos(\phi) \]
\[ \phi=\cos^{-1}(PF) \]

This relationship is most meaningful for sinusoidal voltage and current waveforms. Nonlinear loads may require true power factor analysis.

Power Factor Correction kVAR

Power factor correction estimates the capacitive kVAR needed to move from an existing power factor to a target power factor.

\[ Q_c=P\left[\tan\left(\cos^{-1}(PF_1)\right)-\tan\left(\cos^{-1}(PF_2)\right)\right] \]

In this formula, \(\phi_1=\cos^{-1}(PF_1)\) is the existing phase angle and \(\phi_2=\cos^{-1}(PF_2)\) is the target phase angle. \(Q_c\) is usually reported in kVAR when \(P\) is entered in kW.

What the Variables Mean

Power factor calculations are usually simple, but the symbols must be used correctly. The most common mistake is mixing up kW, kVA, and kVAR.

Power factor formula symbols and meanings
SymbolMeaningHow to Use It
\(PF\)Power factor, the ratio of real power to apparent power.Enter as a decimal such as 0.85 or as a percent such as 85% when the calculator allows it.
\(P\)Real power, also called active power.Use W, kW, or MW. For most facility calculations, kW is common.
\(S\)Apparent power, the RMS AC power demand.Use VA, kVA, or MVA. Apparent power must be greater than or equal to real power.
\(Q\)Reactive power magnitude.Use VAR, kVAR, or MVAR. Enter magnitude unless a sign convention is explicitly required.
\(Q_c\)Capacitive correction reactive power.Use kVAR for capacitor bank correction estimates.
\(V\)RMS AC voltage.Use volts or kilovolts. Confirm whether the system is single-phase or three-phase.
\(V_{LL}\)Three-phase line-to-line RMS voltage.Use for phase-to-phase voltage measurements such as 208 V, 480 V, or 13.8 kV systems.
\(V_{LN}\)Three-phase line-to-neutral RMS voltage.Use only when the calculation mode expects line-to-neutral voltage.
\(I\)RMS line current.Use amps or kiloamps. For three-phase systems, use line current rather than phase winding current unless the method says otherwise.
\(\phi\)Phase angle between voltage and current.Calculated from \(\phi=\cos^{-1}(PF)\).

How to Use the Calculator

Choose the solve mode that matches your known values. The fastest path is usually kW and kVA, but field measurements often require kW, voltage, current, phase type, and voltage convention.

1

Choose what you want to solve for

Select power factor, apparent power, real power, reactive power, line current, or correction kVAR depending on the unknown value.

2

Pick the input method

For power factor, use kW/kVA when apparent power is known, kW/kVAR when reactive power is known, or voltage/current when you have field measurements.

3

Confirm phase and voltage type

For three-phase inputs, verify whether voltage is line-to-line or line-to-neutral. This single setting can change the apparent power calculation significantly.

4

Review the result and quick checks

Check the main answer, phase angle, kVA, kVAR, current, and warning messages. If power factor is greater than 1, the input set is physically inconsistent.

How to Interpret the Result

Power factor shows how effectively apparent power is converted into useful real power. A high power factor means less reactive demand for the same kW load, while a low power factor means more current and kVA are required.

How to interpret power factor calculator results
Result PatternWhat It May MeanWhat to Check Next
\(PF \approx 1.00\)Nearly all apparent power is converted into real power.Check for overcorrection if capacitors are installed and load varies.
\(0.95 \le PF < 1.00\)Strong power factor for many commercial and industrial systems.Confirm utility requirements and whether this target is appropriate for the load profile.
\(0.85 \le PF < 0.95\)Moderate power factor. Correction may or may not be worthwhile.Check demand charges, kVAR demand, transformer loading, and utility penalties.
\(PF < 0.85\)Low power factor, commonly associated with inductive loads.Investigate motors, transformers, underloaded equipment, and power factor correction options.
\(PF > 1.00\)Invalid input set. Real power cannot exceed apparent power.Check units, phase type, voltage convention, current, and whether all measurements are from the same load condition.

What Is a Good Power Factor?

A good power factor is usually close to 1.0. In many commercial and industrial settings, values around 0.95 or higher are often considered strong, but the correct target depends on utility tariffs, equipment, load profile, harmonics, and whether the system risks overcorrection.

What to do with the result

If the result is low, first confirm the inputs are correct. If the system is truly operating at low lagging power factor, review whether capacitor correction, motor loading improvements, or equipment changes could reduce kVA demand and current. If harmonics are significant, do not assume a simple capacitor bank is the correct solution.

What changes the result most?

Apparent power drives the power factor result. In voltage-current calculations, the biggest source of error is often choosing the wrong phase type or voltage convention. In direct power calculations, the biggest source of error is mixing W with kW, VA with kVA, or VAR with kVAR.

Lagging vs. Leading Power Factor

A lagging power factor usually means current lags voltage, which is common with inductive loads such as motors, transformers, and magnetic equipment. A leading power factor means current leads voltage, which can occur with capacitive loads or overcorrected systems.

Quick sanity check

A valid power factor magnitude should be between 0 and 1. If \(P>S\), \(PF>1\), or the current seems far too high, recheck the unit selectors, line-to-line versus line-to-neutral voltage, and whether the measured values came from the same operating point.

Input Quality Checklist

Good power factor results depend on matching the right values, units, and measurement conditions. Most wrong answers come from inconsistent inputs rather than a complex formula error.

Check Power Type

Confirm whether the value is real power \(P\), apparent power \(S\), or reactive power \(Q\). Do not substitute kW for kVA or kVAR.

Check Unit Scale

Make sure W, kW, MW, VA, kVA, MVA, VAR, kVAR, and MVAR are selected correctly before trusting the result.

Check Phase Type

Use single-phase formulas for single-phase systems and three-phase formulas for balanced three-phase systems.

Check Voltage Convention

For three-phase systems, line-to-line voltage and line-to-neutral voltage are not interchangeable.

Check Measurement Timing

Use kW, kVA, kVAR, voltage, and current from the same load condition. Do not mix nameplate and live measured values without context.

Check Motor Loading

Motor nameplate values are not always the same as operating values. An underloaded motor may have a lower power factor than expected.

Step-by-Step Worked Example

This example calculates power factor for a balanced three-phase load from real power, line-to-line voltage, and line current.

Example Scenario

Real Power
\(P=200\,kW\)
Voltage
\(V_{LL}=480\,V\)
Line Current
\(I=300\,A\)

Calculate Apparent Power

\[ S=\frac{\sqrt{3}V_{LL}I}{1000} \]

Substitute Values

\[ S=\frac{\sqrt{3}(480)(300)}{1000}=249.4\,kVA \]

Calculate Power Factor

\[ PF=\frac{P}{S}=\frac{200}{249.4}=0.802 \]

Result

Power factor: approximately 0.80. If the load is mostly inductive, this would usually be described as about 0.80 lagging.

Is the answer reasonable?

Yes. A 200 kW load drawing about 249.4 kVA has a power factor near 0.80, which means the system is drawing significantly more apparent power than useful real power. This is a realistic result for a large inductive load, but it should be checked against actual metering and load profile data before correction equipment is selected.

Power Triangle Diagram

The power triangle shows the relationship between real power, reactive power, apparent power, phase angle, and power factor. It is the core visual model behind most power factor calculations.

Power triangle diagram showing real power P, reactive power Q, apparent power S, phase angle phi, and the power factor relationship PF equals P divided by S.
The AC power triangle shows \(P\) on the horizontal axis, \(Q\) on the vertical axis, and \(S\) as the hypotenuse. Power factor is \(PF=P/S=\cos(\phi)\), so a smaller phase angle means less reactive power for the same real power.

Typical Power Factor Values and Reference Ranges

Typical power factor ranges are useful for quick screening, but acceptable values depend on utility rules, equipment type, load profile, and whether harmonic distortion is present.

Typical power factor interpretation ranges
Power Factor RangeTypical InterpretationHow to Use It
0.98 to 1.00Excellent displacement power factor.Check for overcorrection if capacitor banks are installed and load varies.
0.95 to 0.98Common practical target range for many correction projects.Often a good target, but verify utility and site requirements.
0.85 to 0.95Moderate range that may be acceptable or may trigger utility penalties.Review kVAR demand, demand charges, transformer loading, and load profile.
Below 0.85Low power factor for many commercial and industrial applications.Investigate inductive loads, underloaded motors, transformers, and correction options.
Greater than 1.00Physically invalid for power factor magnitude.Check units, phase selection, voltage type, current, and inconsistent measurements.

Design Ranges and Practical Checks

A mathematically correct power factor result is not always enough for design. Real systems need practical targets, load profile review, and checks for harmonics or switching behavior.

Low Power Factor

Low power factor increases kVA and current for the same kW load, which can affect transformers, conductors, voltage drop, and utility billing.

Practical Correction Target

Many correction projects target a high but not perfect power factor, often around 0.95 to 0.98, depending on the utility tariff and load behavior.

Too Close to Unity

Correcting too close to 1.0 can increase overcorrection risk during light-load conditions or when capacitor stages remain energized after the load drops.

How Power Factor Correction kVAR Works

Power factor correction adds capacitive reactive power to reduce the lagging reactive demand of an inductive load. The real power \(P\) usually stays about the same, but apparent power \(S\), reactive power \(Q\), and line current may decrease.

Typical before-and-after effect of power factor correction
Before CorrectionAfter CorrectionWhy It Matters
Lower power factorHigher power factorMore apparent power is converted into useful real power.
Higher net kVAR demandLower net kVAR demandCapacitors offset part of the inductive reactive demand.
Higher kVA for the same kWLower kVA for the same kWTransformer and electrical capacity may be used more effectively.
Higher line currentLower line currentLower current can reduce voltage drop and some system losses.

Does correcting power factor reduce kWh?

Power factor correction usually reduces kVA demand and line current, but it does not directly reduce the real power required by the load. It may reduce some system losses, but the main financial benefit often depends on utility demand charges or power factor penalties.

Engineering judgment check

Do not size capacitors from one operating point alone when the load changes throughout the day. Review measured demand data, kVAR trends, switching stages, harmonic distortion, resonance risk, voltage rating, protection requirements, and utility rules before final equipment selection.

Unit Conversion Notes

Unit mistakes are one of the most common causes of incorrect power factor results. Keep real power, apparent power, and reactive power in compatible scales before comparing them.

Common unit conversions for power factor calculations
QuantityCommon UnitsConversion Reminder
Real PowerW, kW, MW\(1\,kW=1000\,W\), \(1\,MW=1000\,kW\)
Apparent PowerVA, kVA, MVA\(1\,kVA=1000\,VA\), \(1\,MVA=1000\,kVA\)
Reactive PowerVAR, kVAR, MVAR\(1\,kVAR=1000\,VAR\), \(1\,MVAR=1000\,kVAR\)
VoltageV, kV\(1\,kV=1000\,V\)
CurrentA, kA\(1\,kA=1000\,A\)

Most common unit trap

Entering watts while the calculator is set to kW, or entering VA while the calculator is set to kVA, can shift the result by a factor of 1,000. If the answer looks impossible, check unit scale before changing the formula.

kW/kVA vs. kW/kVAR vs. Voltage and Current

The best calculation method depends on the values you actually know. Use direct kW/kVA when apparent power is available, kW/kVAR for power triangle data, and voltage-current formulas for field measurements.

Comparison of power factor calculation methods
MethodBest ForInputs NeededMain Caution
kW and kVAFastest method when real and apparent power are already known.\(P\) and \(S\)\(P\) cannot exceed \(S\).
kW and kVARPower triangle calculation when reactive power is known.\(P\) and \(Q\)Reactive power should be treated consistently as a magnitude or signed value.
kW, voltage, and currentField measurement checks from metering, voltage, and current.\(P\), \(V\), and \(I\)Phase type and voltage convention must be correct.
Correction kVAREstimating capacitor correction to move from existing PF to target PF.\(P\), \(PF_1\), and \(PF_2\)Does not replace harmonic, resonance, utility, or equipment review.

Common Mistakes That Cause Wrong Results

Most power factor errors come from wrong units, wrong phase assumptions, or values taken from different operating conditions. The formula is usually not the problem.

Common Mistakes

  • Using kW where kVA is required, or kVA where kW is required.
  • Entering W, VA, or VAR while the unit selector is set to kW, kVA, or kVAR.
  • Using line-to-neutral voltage in a line-to-line three-phase formula.
  • Combining nameplate current with measured kW from a different load condition.
  • Assuming capacitor correction is safe without checking harmonics or resonance.
  • Trying to correct every system exactly to 1.0 power factor.

Better Practice

  • Confirm whether each value is real, apparent, or reactive power.
  • Check unit selectors before trusting the result.
  • Use the correct single-phase or three-phase formula.
  • Verify line-to-line versus line-to-neutral voltage before using current-based methods.
  • Use measured load data when evaluating an operating facility.
  • Target a practical corrected power factor based on utility and equipment requirements.

Troubleshooting Unexpected Results

If a power factor result looks wrong, start by checking whether the input set is physically possible. Real power cannot be greater than apparent power for a valid power factor magnitude.

Common power factor result problems and fixes
ProblemLikely CauseFix
Power factor is greater than 1Real power exceeds apparent power because of wrong units or inconsistent inputs.Check kW, kVA, phase type, voltage, current, and unit selectors.
Current seems too highVoltage is low, power is high, power factor is low, or the phase setting is wrong.Verify voltage convention and whether the load is single-phase or three-phase.
Correction kVAR seems too largeExisting power factor is very low, target PF is too close to 1.0, or real power is entered in the wrong unit.Try a practical target such as 0.95 or 0.98 and review measured kVAR demand.
Result does not match another calculatorDifferent rounding, voltage convention, phase assumption, or true PF versus displacement PF assumptions.Compare formulas and confirm line-to-line versus line-to-neutral voltage.
Power factor looks good but utility penalties remainThe utility may use a different measurement window, kVAR demand method, or tariff rule.Review utility billing data and measured demand intervals instead of one snapshot.

Common edge cases

VFDs, rectifiers, UPS systems, LED drivers, nonlinear loads, and harmonic-rich facilities may have true power factor behavior that is not fully described by displacement power factor alone. For those systems, use measured power quality data before selecting correction equipment.

Assumptions, Sources, and Limitations

This calculator uses standard steady-state AC power relationships for educational estimates, troubleshooting, and preliminary engineering checks.

Formula Assumption

The formulas assume RMS AC values and standard sinusoidal power triangle relationships.

Input Assumption

Voltage, current, kW, kVA, and kVAR should represent the same load and the same operating condition.

Power Factor Type

The calculation is best interpreted as displacement-style power factor unless the measured inputs already include true power factor effects.

Application Limit

The calculator does not perform harmonic analysis, resonance analysis, switching transient analysis, utility tariff optimization, or protection coordination.

True Power Factor vs. Displacement Power Factor

Displacement power factor is based on the phase angle between voltage and current at the fundamental frequency. True power factor also accounts for waveform distortion from nonlinear loads. If a facility has VFDs, rectifiers, UPS systems, LED drivers, or high harmonic distortion, true power factor may differ from the simple power triangle result.

Calculation basis and final design caution

This page uses standard AC power relationships: \(PF=P/S\), \(S=\sqrt{P^2+Q^2}\), \(PF=\cos(\phi)\), \(S=\sqrt{3}V_{LL}I/1000\), and \(Q_c=P[\tan(\phi_1)-\tan(\phi_2)]\). For final electrical design, verify results against project requirements, applicable electrical codes, utility rules, manufacturer capacitor bank data, switching stage requirements, harmonic conditions, equipment ratings, and qualified engineering judgment.

Related Calculators and Next Steps

Use related electrical calculators to continue the workflow after checking power factor, current, apparent power, or correction kVAR.

Glossary of Terms

These definitions explain the main terms used in power factor calculations without requiring a separate electrical theory reference.

Power Factor

The ratio of real power to apparent power. It describes how effectively AC power is converted into useful work.

Real Power

Power that performs useful work, usually measured in watts or kilowatts.

Apparent Power

The total RMS AC power demand, measured in VA or kVA.

Reactive Power

Power exchanged between the source and reactive components, measured in VAR or kVAR.

Lagging Power Factor

A condition where current lags voltage, commonly associated with inductive loads such as motors and transformers.

Leading Power Factor

A condition where current leads voltage, often associated with capacitive effects or overcorrection.

Correction kVAR

The capacitive reactive power added to reduce lagging reactive demand and improve power factor.

Power Triangle

A right-triangle model connecting real power, reactive power, apparent power, phase angle, and power factor.

Frequently Asked Questions

What does the Power Factor Calculator calculate?

The Power Factor Calculator helps calculate power factor, apparent power, real power, reactive power, line current, phase angle, and correction kVAR depending on the selected solve mode and known inputs.

What is the basic power factor formula?

The basic formula is \(PF=P/S\), where \(P\) is real power and \(S\) is apparent power.

How do you calculate power factor from kW and kVAR?

To calculate power factor from kW and kVAR, first calculate apparent power with \(S=\sqrt{P^2+Q^2}\), then calculate \(PF=P/S\). Combined into one formula, \(PF=P/\sqrt{P^2+Q^2}\).

Why is my power factor greater than 1?

A power factor greater than 1 usually means the input values are inconsistent. Real power cannot exceed apparent power, so check whether kW, kVA, voltage, current, phase type, or unit settings were entered incorrectly.

What is a good power factor?

A power factor closer to 1.0 is better. Many commercial and industrial systems target roughly 0.95 to 0.98, but the correct target depends on utility requirements, equipment, load profile, harmonic distortion, and engineering review.

Does power factor correction reduce kWh?

Power factor correction usually reduces kVA demand and line current, but it does not directly reduce the real power required by the load. It may reduce some system losses, but the main financial benefit often depends on utility demand charges or power factor penalties.

Scroll to Top