Voltage Drop Calculation Table

Compare voltage drop from 18 AWG through 1000 kcmil and find the first listed conductor that meets your voltage, current, one-way distance, circuit, material, and drop target.

Voltage Drop Calculation Table by Wire Size

Enter one circuit scenario, then compare every listed conductor size at once. The highlighted row is the first size that meets the selected voltage-drop target—not a final ampacity approval.

Default reference · 120 V · 15 A · 50 ft one-way · copper · single-phase · 3% target

12 AWG 2.47% drop · 2.963 V · 117.04 V at load First listed conductor that meets the default voltage-drop target. Verify ampacity separately.

The table can scroll horizontally on smaller screens. The wire-size column stays available as the row identifier.

Voltage-drop comparison for standard 18 AWG through 1000 kcmil conductor sizes. Default values are 120 V, 15 A, 50 ft one-way, copper, single-phase AC, and a 3% target.
Target status
18 AWG 9.95% 11.944 V 108.06 V 15.1 ft > 3% target 179.2 W 1,620 / 0.82
16 AWG 6.25% 7.500 V 112.50 V 24.0 ft > 3% target 112.5 W 2,580 / 1.31
14 AWG 3.92% 4.708 V 115.29 V 38.2 ft > 3% target 70.6 W 4,110 / 2.08
12 AWG 2.47% 2.963 V 117.04 V 60.7 ft Minimum by drop 44.4 W 6,530 / 3.31
10 AWG 1.55% 1.864 V 118.14 V 96.6 ft ≤ 3% target 28.0 W 10,380 / 5.26
8 AWG 0.98% 1.172 V 118.83 V 153.6 ft ≤ 3% target 17.6 W 16,510 / 8.37
6 AWG 0.61% 0.737 V 119.26 V 244.1 ft ≤ 3% target 11.1 W 26,240 / 13.30
4 AWG 0.39% 0.464 V 119.54 V 388.3 ft ≤ 3% target 7.0 W 41,740 / 21.15
3 AWG 0.31% 0.368 V 119.63 V 489.5 ft ≤ 3% target 5.5 W 52,620 / 26.66
2 AWG 0.24% 0.292 V 119.71 V 617.3 ft ≤ 3% target 4.4 W 66,360 / 33.63
1 AWG 0.19% 0.231 V 119.77 V 778.5 ft ≤ 3% target 3.5 W 83,690 / 42.41
1/0 AWG 0.15% 0.183 V 119.82 V 982.3 ft ≤ 3% target 2.7 W 105,600 / 53.51
2/0 AWG 0.12% 0.145 V 119.85 V 1238.1 ft ≤ 3% target 2.2 W 133,100 / 67.44
3/0 AWG 0.10% 0.115 V 119.88 V 1560.9 ft ≤ 3% target 1.7 W 167,800 / 85.03
4/0 AWG 0.08% 0.091 V 119.91 V 1968.4 ft ≤ 3% target 1.4 W 211,600 / 107.22
250 kcmil 0.06% 0.077 V 119.92 V 2325.6 ft ≤ 3% target 1.2 W 250,000 / 126.68
300 kcmil 0.05% 0.065 V 119.94 V 2790.7 ft ≤ 3% target 1.0 W 300,000 / 152.01
350 kcmil 0.05% 0.055 V 119.94 V 3255.8 ft ≤ 3% target 0.8 W 350,000 / 177.35
400 kcmil 0.04% 0.048 V 119.95 V 3720.9 ft ≤ 3% target 0.7 W 400,000 / 202.68
500 kcmil 0.03% 0.039 V 119.96 V 4651.2 ft ≤ 3% target 0.6 W 500,000 / 253.35
600 kcmil 0.03% 0.032 V 119.97 V 5581.4 ft ≤ 3% target 0.5 W 600,000 / 304.02
750 kcmil 0.02% 0.026 V 119.97 V 6976.7 ft ≤ 3% target 0.4 W 750,000 / 380.03
1000 kcmil 0.02% 0.019 V 119.98 V 9302.3 ft ≤ 3% target 0.3 W 1,000,000 / 506.71

Calculated values use the simplified circular-mil K-factor method for preliminary comparison. Actual conductor resistance and impedance vary with temperature, conductor construction, installation method, AC effects, and source data. Ampacity is a separate design check.

Scenario: 120 V, 15 A, 50 ft one-way, copper, single-phase AC, 3.00% maximum drop. Voltage-drop screening only; verify ampacity separately.

Share, export, and print

How to Read the Voltage Drop Table

Red rows: exceed the selected voltage-drop targetHighlighted row: smallest listed size at or below the targetLarger conductors: produce lower calculated dropFinal design: must also satisfy ampacity and installation rules

The highlighted row answers one specific question: which listed conductor first meets the selected voltage-drop percentage under the entered assumptions. It does not determine the final conductor size by itself.

Voltage drop is not an ampacity check

A row can pass the selected voltage-drop target and still be unacceptable for installation. Verify conductor ampacity, overcurrent protection, insulation and terminal temperature ratings, correction factors, raceway fill, grounding, equipment instructions, and the locally adopted electrical code separately.

Enter One-Way Distance, Not Round-Trip Length

The length input is the source-to-load distance once. The calculation applies the required circuit multiplier internally, so do not double the entered distance.

Single-phase / two-wire DC: the formula uses a factor of 2. Balanced three-phase: the simplified formula uses √3.

3% and 5% Voltage Drop Guidance

Three percent is a common design target for an individual branch circuit, while five percent is often used as a combined feeder-plus-branch design target. These values should not be treated as one universal legal limit for every circuit or piece of equipment.

Allowable voltage drop in volts at common source voltages.
Source voltage1%2%3%5%
12 V0.12 V0.24 V0.36 V0.60 V
24 V0.24 V0.48 V0.72 V1.20 V
48 V0.48 V0.96 V1.44 V2.40 V
120 V1.20 V2.40 V3.60 V6.00 V
208 V2.08 V4.16 V6.24 V10.40 V
240 V2.40 V4.80 V7.20 V12.00 V
277 V2.77 V5.54 V8.31 V13.85 V
480 V4.80 V9.60 V14.40 V24.00 V

Voltage Drop Equations Used by This Table

For a two-wire DC or single-phase circuit, the preliminary circular-mil relationship is:

Single-phase or two-wireVd = 2KIL ÷ CM

The entered length is one-way. The factor of 2 represents the outgoing and return conductor path.

For a balanced three-phase circuit:

Balanced three-phaseVd = √3KIL ÷ CM

The result is an approximate line-to-line voltage drop for balanced loading.

Variables

  • Vdvoltage drop, volts
  • Kmaterial resistivity constant in ohm-cmil/ft
  • Iload current, amperes
  • Lone-way length, feet
  • CMconductor area, circular mils

Percentage drop is calculated as 100 × Vd ÷ source voltage. The solver keeps full internal precision and rounds only the displayed values.

Voltage Drop Calculation Examples

120 V, 15 A, 50 ft copper

12 AWG: Vd = 2 × 12.9 × 15 × 50 ÷ 6,530 ≈ 2.96 V, or 2.47%.

At a 3% target, 14 AWG is above the target and 12 AWG is the smallest listed size below it by voltage drop alone.

240 V, 30 A, 150 ft copper

8 AWG: Vd = 2 × 12.9 × 30 × 150 ÷ 16,510 ≈ 7.03 V, or 2.93%.

10 AWG is above a 3% target in this simplified comparison, while 8 AWG is below it.

480 V, 50 A, 250 ft three-phase copper

6 AWG: Vd = √3 × 12.9 × 50 × 250 ÷ 26,240 ≈ 10.64 V, or 2.22%.

8 AWG is above a 3% target in this simplified balanced three-phase comparison; 6 AWG is below it.

Common Voltage Drop Calculation Mistakes

Entering round-trip length

This tool expects one-way source-to-load distance and applies the circuit multiplier internally.

Using breaker rating automatically

Use the design or operating current appropriate to the engineering check. Breaker rating and actual load current are not always interchangeable.

Ignoring feeder drop

A branch-circuit target does not erase voltage drop already consumed upstream in a feeder.

Rounding too early

Target status is evaluated from the unrounded result, even when the displayed percentage appears equal to the target.

Assuming copper and aluminum are interchangeable

Different material constants change the calculated drop and may change the minimum listed size by voltage drop.

Treating the result as approval

The table is a preliminary design aid, not a substitute for project-specific engineering or code review.

Engineering Basis and Source Transparency

Original calculated output; no complete NEC or IEEE conductor table is reproduced.

This table uses the simplified circular-mil K-factor method for preliminary voltage-drop comparison. Detailed AC design can require verified conductor resistance, reactance, temperature, installation configuration, power factor, harmonics, and equipment-specific limits.

Dataset and Review Details

Publisher
Turn2Engineering
Calculation basis
2KIL/CM and √3KIL/CM
Default K values
Copper 12.9; aluminum 21.2 ohm-cmil/ft, used as simplified design constants
Length convention
One-way input
Conductor range
18 AWG through 1000 kcmil; metric area shown as an approximate conversion
Rights status
Original calculated comparison; restricted standards tables excluded
Known exclusions
Temperature-adjusted AC impedance, harmonics, parallel runs, motor starting, nonlinear loads

Voltage Drop Calculation Table FAQs

Enter the one-way distance from source to load. The table applies a factor of 2 for a two-wire or single-phase path and √3 for a balanced three-phase calculation.