Primary reference
AWG diameter and area table
Calculated nominal geometry for solid round wire.
Search a gauge such as “12 AWG,” filter by size band, or open advanced tools to find gauges near a target cross-sectional area. Select rows to compare them in the chart.
No AWG sizes match the current filters.
Scroll horizontally to view additional columns and vertically to view additional rows. Column headers remain visible while scrolling.
| Compare | Copy | ||||||
|---|---|---|---|---|---|---|---|
| 4/0 | -3 | 0.4600 | 11.684 | 211,600 | 107.2 | ||
| 3/0 | -2 | 0.4096 | 10.405 | 167,806 | 85.0 | ||
| 2/0 | -1 | 0.3648 | 9.266 | 133,077 | 67.4 | ||
| 1/0 | 0 | 0.3249 | 8.251 | 105,535 | 53.5 | ||
| 1 | 1 | 0.2893 | 7.348 | 83,693 | 42.4 | ||
| 2 | 2 | 0.2576 | 6.544 | 66,371 | 33.6 | ||
| 3 | 3 | 0.2294 | 5.827 | 52,635 | 26.7 | ||
| 4 | 4 | 0.2043 | 5.189 | 41,741 | 21.2 | ||
| 5 | 5 | 0.1819 | 4.621 | 33,102 | 16.8 | ||
| 6 | 6 | 0.1620 | 4.115 | 26,251 | 13.3 | ||
| 7 | 7 | 0.1443 | 3.665 | 20,818 | 10.5 | ||
| 8 | 8 | 0.1285 | 3.264 | 16,510 | 8.37 | ||
| 9 | 9 | 0.1144 | 2.906 | 13,093 | 6.63 | ||
| 10 | 10 | 0.1019 | 2.588 | 10,383 | 5.26 | ||
| 11 | 11 | 0.09074 | 2.305 | 8,234 | 4.17 | ||
| 12 | 12 | 0.08081 | 2.053 | 6,530 | 3.31 | ||
| 13 | 13 | 0.07196 | 1.828 | 5,178 | 2.62 | ||
| 14 | 14 | 0.06408 | 1.628 | 4,107 | 2.08 | ||
| 15 | 15 | 0.05707 | 1.450 | 3,257 | 1.65 | ||
| 16 | 16 | 0.05082 | 1.291 | 2,583 | 1.31 | ||
| 17 | 17 | 0.04526 | 1.150 | 2,048 | 1.04 | ||
| 18 | 18 | 0.04030 | 1.024 | 1,624 | 0.823 | ||
| 19 | 19 | 0.03589 | 0.9116 | 1,288 | 0.653 | ||
| 20 | 20 | 0.03196 | 0.8118 | 1,022 | 0.518 | ||
| 21 | 21 | 0.02846 | 0.7229 | 810 | 0.410 | ||
| 22 | 22 | 0.02535 | 0.6438 | 642 | 0.326 | ||
| 23 | 23 | 0.02257 | 0.5733 | 509 | 0.258 | ||
| 24 | 24 | 0.02010 | 0.5106 | 404 | 0.205 | ||
| 25 | 25 | 0.01790 | 0.4547 | 320 | 0.162 | ||
| 26 | 26 | 0.01594 | 0.4049 | 254 | 0.129 | ||
| 27 | 27 | 0.01420 | 0.3606 | 202 | 0.102 | ||
| 28 | 28 | 0.01264 | 0.3211 | 160 | 0.0810 | ||
| 29 | 29 | 0.01126 | 0.2859 | 127 | 0.0642 | ||
| 30 | 30 | 0.01003 | 0.2546 | 101 | 0.0509 | ||
| 31 | 31 | 0.008928 | 0.2268 | 80 | 0.0404 | ||
| 32 | 32 | 0.007950 | 0.2019 | 63 | 0.0320 | ||
| 33 | 33 | 0.007080 | 0.1798 | 50 | 0.0254 | ||
| 34 | 34 | 0.006305 | 0.1601 | 40 | 0.0201 | ||
| 35 | 35 | 0.005615 | 0.1426 | 32 | 0.0160 | ||
| 36 | 36 | 0.005000 | 0.1270 | 25 | 0.0127 | ||
| 37 | 37 | 0.004453 | 0.1131 | 20 | 0.0100 | ||
| 38 | 38 | 0.003965 | 0.1007 | 16 | 0.0080 | ||
| 39 | 39 | 0.003531 | 0.0897 | 12 | 0.0063 | ||
| 40 | 40 | 0.003145 | 0.0799 | 10 | 0.0050 |
Values describe the nominal bare conductor geometry of a solid round wire. Insulation thickness, finished cable outside diameter, strand construction, resistance, temperature rating, and allowable ampacity are outside this table’s scope.
Area lookup and table actions
Interactive comparison
Compare selected AWG sizes
See how diameter or cross-sectional area changes across selected gauges.
Select two or more gauges in the table to compare them.
How to read the scale
A larger AWG number means a smaller wire
- Gauge direction: 4/0 is the largest size shown; 40 AWG is the smallest.
- Six-gauge shortcut: moving six gauge numbers changes diameter by about a factor of two; area changes by about a factor of four.
- Three-gauge shortcut: moving three sizes changes cross-sectional area by about a factor of two.
- Designation: 1/0, 2/0, 3/0, and 4/0 are also called one-aught through four-aught.
What this chart does—and does not—select
This chart answers a geometry question: the nominal diameter and metallic cross-sectional area associated with an AWG designation. It does not determine whether a conductor is suitable for a circuit.
Design boundary
Do not infer ampacity from diameter alone. Conductor material, insulation temperature rating, number of current-carrying conductors, ambient temperature, installation method, terminal ratings, voltage drop, and governing code all affect a final wire selection.
AWG formula and unit conversions
The AWG progression is geometric. With n = 36 for 36 AWG, n = 0 for 1/0, and negative indices for larger aught sizes, the nominal diameter is:
The endpoints are 0.005 inch at 36 AWG and 0.460 inch at 4/0 AWG.
- Diameter conversion
- dmm = 25.4 × din
- Circular mils
- cmil = (1,000 × din)²
- Metric area
- A = πdmm² / 4
Calculations use unrounded formula values internally; displayed values are rounded only at the end. Circular mil is an area unit, even though its definition uses a diameter measured in mils.
Worked AWG lookup examples
Convert 12 AWG to metric area
The table gives a nominal diameter of 2.053 mm. Applying A = πd²/4 gives about 3.31 mm². This is metallic area, not insulated cable outside diameter.
Find a gauge near 2.5 mm²
Enter 2.5 in Minimum area. The nearest listed nominal area is 13 AWG at about 2.62 mm²; 14 AWG is about 2.08 mm². A code-compliant conductor choice still requires the applicable ampacity and installation rules.
Compare 10 and 16 AWG
10 AWG is about 2.588 mm in diameter and 5.26 mm² in area; 16 AWG is about 1.291 mm and 1.31 mm². Six gauge steps nearly halve diameter and quarter area.
AWG data basis and engineering references
Dataset scope: formula-derived nominal geometry for 44 solid round-wire sizes, 4/0 through 40 AWG.
The page uses the defining AWG geometric progression and calculates the converted fields shown in the table. It does not reproduce resistance, mass, strength, or ampacity tables.
- ASTM B258-18(2026), Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical ConductorsCurrent standard scope and controlling subject. Access to the complete ASTM standard may require purchase.
- NBS Handbook 100, Copper Wire TablesPublic-domain historical reference describing the AWG progression, nominal diameter conventions, units, and conductor-property context.
Dataset and source-check details
- Edition / formulation
- ASTM B258-18(2026) scope; AWG geometric progression from 4/0 to 40
- Source-controlled fields
- ASTM subject scope; NBS Handbook 100 gauge endpoints, progression, and unit conventions
- Calculated fields
- Diameter conversions, circular mils, and square-millimeter area
- Reference conditions
- Nominal bare solid round-wire geometry
- Known exclusions
- Ampacity, resistance, material, stranding, insulation, cable OD, and code selection
- Rights / download
- Original calculated dataset; visible-row CSV permitted with source attribution retained on page
- Source check
- Source scope checked August 9, 2026
- Publisher
- Turn2Engineering
AWG wire size questions
No. AWG numbering runs in the opposite direction: a higher gauge number means a smaller conductor diameter and area.
Yes. The standard designation is commonly written 1/0 AWG and spoken “one aught.” The formula index for 1/0 is zero.
No. AWG describes conductor geometry. Insulation, jackets, shielding, strand lay, and manufacturer construction increase the finished cable outside diameter.
Not by itself. Ampacity requires conductor material, temperature rating, installation conditions, adjustment factors, terminal limitations, and the applicable electrical code.
A circular mil is the area of a circle one mil—0.001 inch—in diameter. For a round wire, circular-mil area equals the diameter in mils squared.
Use geometry first, then verify the electrical design
Use this AWG wire size chart to translate a gauge designation into nominal solid-wire diameter and area or to locate the closest listed geometry. For an actual circuit, continue with ampacity, voltage-drop, terminal, insulation, raceway-fill, and code checks.