AWG Wire Size Chart

Compare AWG wire sizes from 4/0 to 40 by bare-conductor diameter in inches and millimeters, cross-sectional area in mm², circular mils, and copper DC resistance at 20°C.

Range
4/0–40 AWG
Basis
Solid round wire
Rows
44 gauge sizes

Visual comparison

How AWG wire sizes compare

Common bare-copper AWG conductors shown at proportional thickness.

Wire specimens are drawn at a common length with conductor thickness scaled to nominal bare solid-wire diameter. The comparison preserves the relative diameter differences between the sizes shown; screen dimensions are not physical size.

Instant lookup

Find an AWG wire size

Choose a gauge to see its nominal bare solid-wire dimensions immediately.

AWG measures the conductor. Diameter values do not include insulation or cable jacket thickness.

12 AWG 2.053 mm bare solid-conductor diameter
Diameter
0.08081 in
Area
3.31 mm²
Circular mils
6,530 cmil
Cu resistance
1.588 Ω/kft
DC at 20°C

Resistance is calculated from the International Annealed Copper Standard resistivity basis at 20°C and the nominal circular-mil area shown in this chart.

Primary reference

Complete AWG Wire Size Chart

Diameter, area, circular mils, and copper resistance from 4/0 through 40 AWG.

Search a gauge or filter the range. Select rows when you want to compare sizes in the interactive chart.

Scroll horizontally to view additional columns and vertically to view additional rows. Column headers remain visible while scrolling.

American Wire Gauge sizes 4/0 through 40 with nominal bare solid-wire diameter, cross-sectional area, circular-mil area, and copper DC resistance at 20°C.
4/0 0.0490 0.4600 11.684 211,600 107.2
3/0 0.0618 0.4096 10.405 167,806 85.0
2/0 0.0779 0.3648 9.266 133,077 67.4
1/0 0.0983 0.3249 8.251 105,535 53.5
1 0.124 0.2893 7.348 83,693 42.4
2 0.156 0.2576 6.544 66,371 33.6
3 0.197 0.2294 5.827 52,635 26.7
4 0.248 0.2043 5.189 41,741 21.2
5 0.313 0.1819 4.621 33,102 16.8
6 0.395 0.1620 4.115 26,251 13.3
7 0.498 0.1443 3.665 20,818 10.5
8 0.628 0.1285 3.264 16,510 8.37
9 0.792 0.1144 2.906 13,093 6.63
10 0.999 0.1019 2.588 10,383 5.26
11 1.260 0.09074 2.305 8,234 4.17
12 1.588 0.08081 2.053 6,530 3.31
13 2.003 0.07196 1.828 5,178 2.62
14 2.525 0.06408 1.628 4,107 2.08
15 3.184 0.05707 1.450 3,257 1.65
16 4.015 0.05082 1.291 2,583 1.31
17 5.063 0.04526 1.150 2,048 1.04
18 6.385 0.04030 1.024 1,624 0.823
19 8.051 0.03589 0.9116 1,288 0.653
20 10.15 0.03196 0.8118 1,022 0.518
21 12.80 0.02846 0.7229 810 0.410
22 16.14 0.02535 0.6438 642 0.326
23 20.36 0.02257 0.5733 509 0.258
24 25.67 0.02010 0.5106 404 0.205
25 32.37 0.01790 0.4547 320 0.162
26 40.81 0.01594 0.4049 254 0.129
27 51.47 0.01420 0.3606 202 0.102
28 64.90 0.01264 0.3211 160 0.0810
29 81.83 0.01126 0.2859 127 0.0642
30 103.19 0.01003 0.2546 101 0.0509
31 130.12 0.008928 0.2268 80 0.0404
32 164.08 0.007950 0.2019 63 0.0320
33 206.90 0.007080 0.1798 50 0.0254
34 260.90 0.006305 0.1601 40 0.0201
35 328.98 0.005615 0.1426 32 0.0160
36 414.84 0.005000 0.1270 25 0.0127
37 523.10 0.004453 0.1131 20 0.0100
38 659.62 0.003965 0.1007 16 0.0080
39 831.77 0.003531 0.0897 12 0.0063
40 1048.84 0.003145 0.0799 10 0.0050

Dimensions describe nominal bare solid round-wire geometry. Copper resistance is a calculated DC reference at 20°C; actual conductor resistance varies with material, temperature, stranding, and manufacturing tolerances. Insulation and cable outside diameter are not included.

Area lookup and table actions

Solid vs. stranded AWG diameter

AWG identifies conductor size, not finished cable outside diameter. The diameter values in this chart represent the nominal geometry of a solid round conductor. A stranded conductor of the same AWG normally has a larger overall conductor diameter because individual strands do not fill a perfect circle, and insulation or jackets add still more outside diameter.

Use manufacturer dimensions for fit. For conduit fill, connectors, glands, terminals, or cable-routing clearances, use the actual insulated conductor or cable outside diameter rather than the bare-solid AWG diameter from this chart.

Metric conversion

AWG ↔ mm² converter

Convert an AWG designation or find the nearest nominal AWG area to a metric target.

AWG to mm²

3.31 mm²2.053 mm diameter

mm² to nearest AWG

13 AWG2.62 mm² nominal area

AWG and metric conductor sizes are different sizing systems. A metric size such as 2.5 mm² is not literally an AWG size; the converter identifies the closest nominal AWG area and shows adjacent sizes for context.

Quick reference

Common AWG wire sizes

Frequently referenced conductor sizes at a glance.

4 AWG
Diameter
5.189 mm
Area
21.2 mm²
Cu @ 20°C
0.248 Ω/kft
6 AWG
Diameter
4.115 mm
Area
13.3 mm²
Cu @ 20°C
0.395 Ω/kft
8 AWG
Diameter
3.264 mm
Area
8.37 mm²
Cu @ 20°C
0.628 Ω/kft
10 AWG
Diameter
2.588 mm
Area
5.26 mm²
Cu @ 20°C
0.999 Ω/kft
12 AWG
Diameter
2.053 mm
Area
3.31 mm²
Cu @ 20°C
1.588 Ω/kft
14 AWG
Diameter
1.628 mm
Area
2.08 mm²
Cu @ 20°C
2.525 Ω/kft
16 AWG
Diameter
1.291 mm
Area
1.31 mm²
Cu @ 20°C
4.015 Ω/kft

How to read the scale

A larger AWG number means a smaller wire

  • Gauge direction: 4/0 is the largest size shown; 40 AWG is the smallest.
  • Six-gauge shortcut: moving six gauge numbers changes diameter by about a factor of two; area changes by about a factor of four.
  • Three-gauge shortcut: moving three sizes changes cross-sectional area by about a factor of two.
  • Designation: 1/0, 2/0, 3/0, and 4/0 are also called one-aught through four-aught.

What this chart does—and does not—select

This chart answers a geometry question: the nominal diameter and metallic cross-sectional area associated with an AWG designation. It does not determine whether a conductor is suitable for a circuit.

Design boundary

Do not infer ampacity from diameter alone. Conductor material, insulation temperature rating, number of current-carrying conductors, ambient temperature, installation method, terminal ratings, voltage drop, and governing code all affect a final wire selection.

AWG formula and unit conversions

The AWG progression is geometric. With n = 36 for 36 AWG, n = 0 for 1/0, and negative indices for larger aught sizes, the nominal diameter is:

Diameter in inchesd = 0.005 × 92(36 − n) / 39

The endpoints are 0.005 inch at 36 AWG and 0.460 inch at 4/0 AWG.

Diameter conversion
dmm = 25.4 × din
Circular mils
cmil = (1,000 × din)²
Metric area
A = πdmm² / 4

Calculations use unrounded formula values internally; displayed values are rounded only at the end. Circular mil is an area unit, even though its definition uses a diameter measured in mils.

Worked AWG lookup examples

Convert 12 AWG to metric area

The table gives a nominal diameter of 2.053 mm. Applying A = πd²/4 gives about 3.31 mm². This is metallic area, not insulated cable outside diameter.

Find a gauge near 2.5 mm²

A target area of 2.5 mm² falls between 13 AWG at about 2.62 mm² and 14 AWG at about 2.08 mm². The nearest nominal AWG by area is 13 AWG. This is a dimensional comparison only, not a code-compliant conductor selection.

Compare 10 and 16 AWG

10 AWG is about 2.588 mm in diameter and 5.26 mm² in area; 16 AWG is about 1.291 mm and 1.31 mm². Six gauge steps nearly halve diameter and quarter area.

AWG data basis and engineering references

Dataset scope: formula-derived nominal geometry for 44 solid round-wire sizes, 4/0 through 40 AWG.

The page uses the defining AWG geometric progression for nominal solid-wire dimensions. Diameter conversions and areas are calculated from that geometry; copper DC resistance is calculated at 20°C from the International Annealed Copper Standard resistivity basis and nominal circular-mil area. Ampacity is intentionally excluded.

Dataset and source-check details

Edition / formulation
ASTM B258-18(2026) scope; AWG geometric progression from 4/0 to 40
Source-controlled fields
ASTM subject scope; NBS Handbook 100 gauge endpoints, progression, and unit conventions
Calculated fields
Diameter conversions, circular mils, square-millimeter area, and copper DC resistance at 20°C
Reference conditions
Nominal bare solid round-wire geometry; copper resistance reference at 20°C
Known exclusions
Ampacity, insulation, cable OD, installation method, terminal limits, and code selection
Rights / download
Original calculated dataset; visible-row CSV permitted with source attribution retained on page
Source check
Source scope and calculations checked September 27, 2026
Publisher
Turn2Engineering

AWG wire size questions

No. AWG numbering runs in the opposite direction: a higher gauge number means a smaller conductor diameter and area.

Use geometry first, then verify the electrical design

Use this AWG wire size chart to translate a gauge designation into nominal solid-wire diameter and area or to locate the closest listed geometry. For an actual circuit, continue with ampacity, voltage-drop, terminal, insulation, raceway-fill, and code checks.