NEMA Starter Size Chart: HP, Amps, Voltage & Phase
Normal full-voltage, non-plugging and non-jogging motor duty. Use the smallest listed size that satisfies the applicable horsepower rating; if nameplate FLA is entered, the finder also checks continuous-current rating.
Instant starter-size finder
What NEMA starter size do I need?
Enter motor data from the nameplate. FLA is optional but gives a stronger screening check.
HP screen only — compare the motor nameplate FLA with the 27 A continuous-current rating before final selection.
No NEMA size matches that search. Clear the search or use the finder above.
Scroll horizontally to compare current and horsepower ratings. Scroll vertically for larger NEMA sizes. Column headers and the NEMA size column remain visible while scrolling.
| Controller Current | 1-Phase Maximum HP | 3-Phase Maximum HP | Copy | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 00 | 9 | 11 | ⅓ | 1 | 1.5 | 1.5 | 1.5 | 2 | 2 | |
| 0 | 18 | 21 | 1 | 2 | 3 | 3 | 5 | 5 | 5 | |
| 1 | 27 | 32 | 2 | 3 | 7.5 | 7.5 | 10 | 10 | 10 | |
| 1P | 36 | 42 | 3 | 5 | — | — | — | — | — | |
| 2 | 45 | 52 | 3 | 7.5 | 10 | 15 | 25 | 25 | 25 | |
| 3 | 90 | 104 | 7.5 | 15 | 25 | 30 | 50 | 50 | 50 | |
| 4 | 135 | 156 | — | — | 40 | 50 | 75 | 100 | 100 | |
| 5 | 270 | 311 | — | — | 75 | 100 | 150 | 200 | 200 | |
| 6 | 540 | 621 | — | — | 150 | 200 | 300 | 400 | 400 | |
| 7 | 810 | 932 | — | — | — | 300 | — | 600 | 600 | |
| 8 | 1,215 | 1,400 | — | — | — | 450 | — | 900 | 900 | |
| 9 | 2,250 | 2,590 | — | — | — | 800 | — | 1,600 | 1,600 | |
These are starter/controller ratings, not motor full-load-current tables, overload settings, breaker or fuse sizes, conductor ampacity, SCCR, coil voltage, or enclosure requirements. Verify the exact starter manufacturer’s listing for the application before specification or installation.
NEMA Starter Size Chart — normal full-voltage, non-plugging/non-jogging controller reference. Verify the exact starter product and all motor branch-circuit requirements.
Page actions
How to Choose a NEMA Starter Size
- Read the motor nameplate: phase, operating voltage, horsepower, and full-load amps (FLA).
- Use the matching phase and voltage column: do not interpolate an unlisted voltage.
- Find the first size that covers the motor horsepower. If nameplate FLA is known, also confirm it does not exceed that size’s continuous-current rating.
- Verify the actual starter product: duty, overload relay, control voltage, enclosure, SCCR, branch protection, and manufacturer application limits are separate checks.
Fast example
A 10 hp, 460 V, three-phase motor reaches the Size 1 normal-duty limit of 10 hp. Size 1 is therefore the first horsepower-qualifying row; its controller ratings are 27 A continuous and 32 A service-limit current.
Starter Size Is Not the Overload, Breaker, or Fuse Size
The NEMA size classifies the starter/controller. It does not finish the motor branch-circuit design.
Starter / contactor
Check the published horsepower rating at the actual phase and voltage, plus continuous current when motor nameplate FLA is known.
Overload relay
Select and set motor overload protection from the motor and equipment requirements. Do not use the starter’s service-limit current as the overload setting.
Branch protection
Fuse or breaker sizing, conductor ampacity, SCCR, coordination, and disconnecting means remain separate design checks.
For the next protection lookup, use the Fuse Size Chart.
Normal Duty, Jogging, Plugging & Unlisted Voltages
This chart uses the published non-plugging and non-jogging horsepower ratings. Repeated jogging, plugging, rapid reversing, reduced-voltage starting, multispeed motors, VFDs, soft starters, DC motors, and IEC contactors require application-specific selection rather than a simple NEMA-size lookup.
200 V vs 208 V
The cited Rockwell table publishes a 200 V column. This page does not automatically relabel or interpolate it as 208 V; verify the chosen manufacturer’s rating for the actual application voltage.
460 V vs 480 V systems
Use the voltage rating stated by the actual starter manufacturer. This reference preserves the source’s published 460 V column rather than creating an estimated 480 V value.
Size 1P
Size 1P is a single-phase-only size in the cited manufacturer data: 36 A continuous, 42 A service limit, 3 hp at 115 V and 5 hp at 230 V.
NEMA Starter Size Examples
10 hp · 460 V · 3-phase
Size 0 is limited to 5 hp at 460 V. Size 1 reaches 10 hp, so Size 1 is the first horsepower-qualifying row.
25 hp · 460 V · 3-phase
Size 1 is limited to 10 hp and Size 2 reaches 25 hp, so Size 2 is the first horsepower-qualifying row.
4 hp · 230 V · 1-phase
Size 1 is limited to 3 hp while Size 1P reaches 5 hp, so Size 1P is the first horsepower-qualifying row.
Engineering References & Data Scope
NEMA ICS 2 rating basis, transformed into a task-focused reference and cross-checked against current manufacturer technical literature.
The controlling NEMA standard is commercially distributed. This page therefore presents a limited transformed lookup for starter sizing rather than reproducing the standard’s full tables, language, or proprietary arrangement.
- NEMA ICS 2:2000 (R2020) — Controllers, Contactors and Overload Relays Rated 600 VControlling rating basis; commercially distributed through ANSI.
- Rockwell Automation Publication 500-TD014D-EN-P — NEMA Contactor and Starter SpecificationsMarch 2023; source for Sizes 00–8, Size 1P, continuous/service-limit current, phase-specific voltage columns, and normal-duty horsepower ratings.
- Rockwell Automation Publication 500-TD013C-EN-P — Feeder Disconnect and Combination Lighting Contactor SpecificationsIndependent Rockwell electrical-rating cross-check that includes the upper Size 9 current and horsepower ratings used here.
- Eaton — NEMA Contactors and Starters Technical InformationIndependent cross-check for NEMA size, current, and horsepower relationships.
- Schneider Electric — Type S Size 1P product dataProduct-level check for the single-phase Size 1P designation and 230 V horsepower rating.
- Publisher
- Turn2Engineering
- Source check
- October 6, 2026
- Duty
- Normal full-voltage, non-plugging/non-jogging
- Phases
- 1-phase and 3-phase where published
- Interpolation
- None
- Missing values
- Em dash = no rating asserted in this reference
NEMA Starter Size FAQs
For the normal-duty reference shown here, 10 hp at 460 V reaches the published Size 1 limit, so Size 1 is the first horsepower-qualifying NEMA size. Verify motor FLA and the actual starter product before final selection.
Size 2 is the first published normal-duty row rated for 25 hp at 460 V three-phase. Its controller continuous-current rating is 45 A.
Size 1P is a single-phase-only size shown in the cited manufacturer data between Sizes 1 and 2. The cited ratings are 36 A continuous, 42 A service-limit, 3 hp at 115 V, and 5 hp at 230 V.
NEMA starters carry both voltage-dependent horsepower ratings and controller current ratings. Use the applicable horsepower rating and verify continuous current against motor nameplate FLA when available; the exact manufacturer listing controls final selection.
This page does not make that substitution automatically. Confirm the chosen starter manufacturer’s horsepower rating for the actual system voltage and application.
No. Starter size, motor overload protection, branch-circuit overcurrent protection, conductor sizing, SCCR, and enclosure selection are separate design checks.