Electrical wiring devices

NEMA Plug Chart

Search common NEMA straight-blade and locking plug/receptacle configurations by designation, voltage, amperage, and grounding.

Standard basis
ANSI/NEMA WD 6-2021
Scope
21 verified families

Lookup table

NEMA Plug and Receptacle Reference Chart

Common independently verified straight-blade and locking families.

Type a designation such as 5-20R, 14-50, or L14-30P, or filter by electrical rating. P means plug; R means receptacle.

Scroll horizontally to view additional columns and vertically to view additional rows. The NEMA configuration column and column headers remain visible while scrolling.

Common NEMA straight-blade and locking configuration families, electrical ratings, conductor arrangement, and P/R designations. This is not a facsimile or complete reproduction of ANSI/NEMA WD 6.
PlugReceptacle
5-15Straight blade125 V15 A23Grounding5-15P5-15R
5-20Straight blade125 V20 A23Grounding5-20P5-20R
5-30Straight blade125 V30 A23Grounding5-30P5-30R
5-50Straight blade125 V50 A23Grounding5-50P5-50R
6-15Straight blade250 V15 A23Grounding6-15P6-15R
6-20Straight blade250 V20 A23Grounding6-20P6-20R
6-30Straight blade250 V30 A23Grounding6-30P6-30R
6-50Straight blade250 V50 A23Grounding6-50P6-50R
10-30Straight blade125/250 V30 A33Non-grounding10-30P10-30R
10-50Straight blade125/250 V50 A33Non-grounding10-50P10-50R
14-20Straight blade125/250 V20 A34Grounding14-20P14-20R
14-30Straight blade125/250 V30 A34Grounding14-30P14-30R
14-50Straight blade125/250 V50 A34Grounding14-50P14-50R
L5-15Locking125 V15 A23GroundingL5-15PL5-15R
L5-20Locking125 V20 A23GroundingL5-20PL5-20R
L5-30Locking125 V30 A23GroundingL5-30PL5-30R
L6-15Locking250 V15 A23GroundingL6-15PL6-15R
L6-20Locking250 V20 A23GroundingL6-20PL6-20R
L6-30Locking250 V30 A23GroundingL6-30PL6-30R
L14-20Locking125/250 V20 A34GroundingL14-20PL14-20R
L14-30Locking125/250 V30 A34GroundingL14-30PL14-30R

Use this chart to identify a NEMA configuration—not to size conductors, overcurrent protection, or approve an installation. Exact geometry and compliance-critical dimensions belong to the current ANSI/NEMA WD 6 standard.

How to Read a NEMA Plug Number

A NEMA designation identifies a wiring-device configuration family. In L14-30P, the L indicates a locking configuration, 14 identifies the configuration series, 30 is the ampere rating, and P identifies a plug. The matching receptacle uses the R suffix.

L prefix
Locking configuration. A designation without L in this chart is straight blade.
Series number
Identifies the voltage/conductor configuration family; it is not itself a voltage value.
Ampere number
The number after the hyphen is the nominal ampere rating for the configuration.
P / R suffix
P = plug. R = receptacle. A family such as 14-30 can refer to the matched P/R configuration pair.

Do not choose by amperage alone. A 30 A device can belong to 125 V, 250 V, or 125/250 V families with different conductor arrangements and incompatible configurations.

Common NEMA Configuration Examples

NEMA 5-20R

20 A, 125 V, 2-pole, 3-wire grounding receptacle. The matching plug designation is 5-20P.

Sanity check: 5-series entries in this table are 125 V configurations; a 250 V load belongs to a different configuration family.

NEMA 14-50R

50 A, 125/250 V, 3-pole, 4-wire grounding receptacle. The four-wire arrangement includes two ungrounded conductors, a neutral, and equipment grounding conductor.

Limitation: this identification does not determine branch-circuit conductor sizing or continuous-load requirements.

NEMA L14-30P

30 A, 125/250 V, 3-pole, 4-wire grounding locking plug. The corresponding receptacle is L14-30R.

Sanity check: L14-30 is not interchangeable with L6-30 even though both can be rated 30 A.

Straight-Blade, Locking, Grounding, Poles, and Wires

Straight blade vs. locking

  • Straight-blade devices connect by insertion/removal.
  • Locking configurations use the L designation and a twist-locking interface.
  • Do not substitute one family for the other with improvised adapters.

Grounding matters

  • Most modern configurations shown are grounding types.
  • The 10-30 and 10-50 rows are explicitly shown as non-grounding configurations.
  • A grounding conductor is not interchangeable with a neutral conductor.

Poles vs. wires

  • Poles describe current-carrying contacts used by the circuit configuration.
  • Wire count includes all conductors represented by the configuration, including grounding where applicable.
  • Confirm equipment nameplate voltage and circuit topology before choosing a device.

Identification is only one design step. Verify conductor ampacity, breaker/fuse requirements, receptacle environmental suitability, equipment instructions, and applicable electrical code separately.

Standard, Source, and Rights Scope

Dataset label: Common NEMA plug/receptacle identification subset verified against ANSI/NEMA WD 6-2021 scope and current manufacturer technical references; source checked August 7, 2026.

ANSI/NEMA WD 6-2021 is the controlling dimensional specification for plugs and receptacles in this scope. This page reorganizes a limited set of independently verified configuration facts for fast lookup and intentionally does not reproduce NEMA’s selection-chart artwork or dimensional drawings.

Dataset and Source-Check Details

Controlling edition
ANSI/NEMA WD 6-2021
Displayed scope
21 common straight-blade and locking configuration families
Units
Nominal volts and amperes; poles and wires are counts
Rights decision
Limited transformed reference only; no full standard-table CSV or proprietary configuration artwork
Publisher
Turn2Engineering
Maintenance trigger
Recheck when ANSI/NEMA WD 6-2026 is actually published

NEMA Plug Chart FAQ

It identifies a 20 A, 125 V, 2-pole, 3-wire grounding receptacle in the NEMA 5-series; the matching plug is 5-20P.

Use the Exact Configuration, Not Just the Amp Rating

Start with the equipment voltage and circuit arrangement, then match the exact NEMA family, ampere rating, grounding arrangement, and P/R device type. Use the table and decoder for identification, then complete conductor, protection, voltage-drop, environmental, and code checks separately.