Electrical grounding and bonding reference

Equipment Grounding Conductor Size Chart

Enter the upstream breaker or fuse rating to find the baseline copper or aluminum wire-type EGC size and see the governing not-exceeding threshold.

Basis
NFPA 70 (2026)
Input
OCPD rating
Range
>0 to 6000 A

OCPD-to-EGC selector

Find the Minimum Equipment Grounding Conductor Size

The selector uses the first listed OCPD threshold equal to or greater than the entered rating. It never rounds down or interpolates conductor sizes.

A 20 A device uses a baseline 12 AWG copper EGC. Enable JavaScript to look up another rating or material.

Limited reference excerpt

Common Equipment Grounding Conductor Sizes

Common OCPD thresholds are shown for quick reference. Use the selector for ratings not included in this limited excerpt.

Choose the first “not exceeding” threshold that is equal to or greater than the OCPD rating. Never select a lower row.

Scroll horizontally to view all material columns. Column headers remain visible while scrolling.

Limited educational excerpt of common OCPD thresholds and baseline wire-type EGC sizes; verify the complete requirement in the adopted NFPA 70 edition.
Minimum wire-type EGC size
CopperAluminum or copper-clad aluminum
1514 AWG12 AWG
2012 AWG10 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
4003 AWG1 AWG

This excerpt is not a grounding electrode conductor table and does not replace special rules, installation restrictions, local amendments, or an effective ground-fault current path review. No standards-derived CSV or bulk table download is provided.

Equipment Grounding Conductor Chart Summary

  • The baseline wire-type EGC lookup starts with the rating or setting of the upstream automatic overcurrent protective device—not normal load current.
  • When the rating lies between listed values, use the first threshold that is equal to or greater than the rating.
  • Copper and aluminum/copper-clad aluminum use separate source columns; do not substitute material by assuming a one-size step.
  • The result is a table starting point. Installation conditions and other NEC provisions can require a different or larger conductor.

Equipment Grounding Conductor vs. Grounding Electrode Conductor

These conductors have different jobs and different sizing provisions. Similar names do not make their tables interchangeable.

Comparison of common grounding, bonding, and grounded-conductor terms.
ConductorPrimary roleDo not size it with this lookup when…
Equipment grounding conductor (EGC)Connects normally non-current-carrying metal parts into the effective ground-fault current path.Special circuit or installation rules govern beyond the basic OCPD lookup.
Grounding electrode conductor (GEC)Connects the grounded system or equipment to the grounding electrode system.Always; GEC sizing is a separate task.
Grounded conductor (neutral)Intentionally carries current under normal operating conditions where the circuit uses it.Always; neutral sizing follows load and system rules.
Equipment bonding jumperConnects portions of the equipment grounding path to maintain continuity.The applicable bonding-jumper provision requires another basis.

How to Use the OCPD Thresholds

  1. Identify the rating or setting of the automatic breaker or fuse ahead of the equipment.
  2. Select copper or aluminum/copper-clad aluminum for the wire-type EGC.
  3. Find the first source threshold not less than the OCPD rating.
  4. Read the conductor designation from the selected material column, then review the conditions that can modify the basic result.

Threshold example: A 50 A OCPD is above the 20 A row, so it advances to the 60 A threshold. The baseline result is 10 AWG copper or 8 AWG aluminum/copper-clad aluminum. It must not be rounded down to a smaller threshold.

When the Basic Table Lookup Is Not Enough

Conditions that require review beyond the baseline OCPD-to-EGC result.
ConditionWhy it mattersNext check
Ungrounded conductors increased in sizeThe wire-type EGC can also require an increase.Review the applicable 250.122 increased-size rule and circular-mil basis.
Motor circuitThe protective device may not be treated like an ordinary branch-circuit breaker.Apply the motor-circuit provisions and the correct protective-device basis.
Multiple circuits in one wiring methodA common EGC is based on the largest applicable upstream device.Identify every circuit and the largest governing OCPD.
Parallel raceways or cablesEach raceway or cable can have distinct conductor requirements.Review the parallel-installation provisions before selecting a conductor.
Feeder tapThe supply-side device ahead of the tap can govern.Apply the feeder-tap EGC rule and conductor-size ceiling.
Long or high-impedance fault pathThe table minimum may not facilitate prompt protective-device operation.Evaluate the effective ground-fault current path with qualified design and AHJ input.
Raceway or cable armor used as the EGCThis lookup returns wire-type conductor sizes only.Verify the wiring method, listing, fittings, length limits, and continuity requirements.

Worked Equipment Grounding Conductor Examples

20 A copper branch circuit

Given: A 20 A upstream OCPD and a copper wire-type EGC.

Method: The entered value exactly matches the 20 A threshold.

Baseline result: 12 AWG copper.

Check: Confirm the adopted edition, wiring method, termination, and that no special condition requires a larger conductor.

50 A rating between thresholds

Given: A 50 A upstream OCPD and a copper wire-type EGC.

Method: Advance to the first threshold not less than 50 A, which is 60 A.

Baseline result: 10 AWG copper.

Check: The result is only the table starting point; do not use the lookup alone for conductor-upsizing or special-circuit conditions.

Copper vs. Aluminum Equipment Grounding Conductors

The source provides separate conductor designations for copper and for aluminum or copper-clad aluminum. The relationship is not a universal one-AWG-step conversion, especially as designations transition from AWG to kcmil.

  • Use the column matching the actual conductor material.
  • Verify installation restrictions, environmental suitability, conductor protection, and minimum-size limitations.
  • Confirm that terminals, connectors, and equipment are listed and identified for the conductor material and size.
  • Do not infer current-carrying ampacity from the EGC designation; that is a separate conductor-sizing task.

NEC Edition, Local Adoption, and AHJ Review

Publication of a newer NEC edition does not mean it governs every project. State, local, and project requirements can use another edition or add amendments.

  1. Identify the code edition adopted at the project location.
  2. Check state and local amendments and project specifications.
  3. Follow listed equipment instructions and conductor-termination restrictions.
  4. Resolve unusual fault-path or installation questions with the designer and authority having jurisdiction.

Engineering References and Data Scope

2026 NEC wire-type equipment grounding conductor threshold lookup; OCPD ratings above 6000 A and non-wire grounding paths are excluded.

The interactive result is a transformed first-qualifying lookup. Only a limited common-rating excerpt is displayed; the complete copyrighted standards table is not reproduced or offered as a download.

Dataset and Source-Check Details

Dataset label
NFPA 70 (2026) Table 250.122 transformed lookup · v1.0
Lookup rule
First verified threshold greater than or equal to the entered OCPD rating
Canonical units
Amperes; exact AWG or kcmil conductor designation
Valid range
Greater than 0 A through 6000 A
Missing values
No interpolation, inferred conversion, or extrapolation
Rights and download
Copyrighted source; limited excerpt and single-result copy only; no CSV
Verification date
August 8, 2026
Source check
NFPA LiNK 2026 edition basis with official CMP-5 development-record cross-check
Publisher
Turn2Engineering

Equipment Grounding Conductor Size FAQs

The baseline table result is 12 AWG copper or 10 AWG aluminum/copper-clad aluminum. Confirm the locally adopted edition, permitted material, wiring method, and any condition requiring additional sizing.

Use the Result as a Verified Starting Point

Start with the upstream OCPD rating, apply the first qualifying threshold, and keep the material column exact. Before specifying the conductor, confirm the adopted code, local amendments, effective fault path, wiring method, and every special condition that applies to the installation.