Cable Sizing Calculator

Calculate recommended cable size from amps, voltage, phase, one-way cable length, conductor material, voltage drop, and ampacity.

Calculator is for informational purposes only. Terms and Conditions

Cable size is selected by checking both adjusted ampacity and voltage drop. The smallest size that passes both checks is recommended.
1

Choose the cable sizing setup

Select the calculation mode, unit layout, circuit type, and load input method.

Use “Size a new cable” when you want the recommended conductor. Use “Check” if you already know the cable size.
Changing this converts the active length value instead of silently changing 100 ft into 100 m.
Voltage drop uses a 2-wire return path for DC and single-phase, and √3 for three-phase.
If you know watts, kW, VA, or hp, the calculator converts power into current first.
2

Enter the known values

Fill in the visible fields. The calculator updates automatically.

Enter the actual load current before any optional continuous-load multiplier.
Use real power for W/kW/hp. Use apparent power for VA/kVA. For hp, the efficiency setting is applied.
Use nominal source voltage. For three-phase, enter line-to-line voltage.
Enter one-way distance from source to load. The return path is handled automatically for DC and single-phase circuits.
Copper has lower resistance than aluminum. Aluminum usually requires a larger conductor for the same voltage drop.
Common educational targets are 3% for a branch circuit and 5% total feeder plus branch, but final limits depend on project requirements and local code.
Only shown in check mode. Choose whether your existing conductor is listed as AWG/kcmil or metric mm².
Check an existing AWG/kcmil cable size against voltage drop and ampacity.
Check an existing metric conductor size against voltage drop and estimated ampacity.
Advanced Options
3

Cable run visual

The length input is one-way distance. The calculator applies the proper voltage-drop path.

Cable sizing voltage drop diagram A source connected to a load by a cable run, showing one-way length, source voltage, voltage drop, and load voltage. SOURCE 240 V LOAD 100 ft one-wayRecommended size: — Voltage drop: —
4

Solution

Recommended size, voltage drop, ampacity check, and practical design notes.

Recommended cable size
Real-time result updates as you type.

Quick checks

  • Load current
  • Design current
  • Voltage drop
  • Voltage at load
  • Adjusted ampacity
  • Power loss

Nearby cable comparison

SizeAmpacityVoltage DropStatus
Enter values to compare nearby cable sizes.

Source, standards, and assumptions

Educational NEC-style estimate

  • Uses common voltage drop equations for DC, single-phase AC, and three-phase AC circuits.
  • Uses built-in conductor resistance and approximate ampacity tables for educational sizing only.
  • Uses a resistance-only voltage-drop estimate. AC reactance is not included.
  • Does not claim final NEC, IEC, BS 7671, or local-code compliance.
  • Final conductor, insulation, terminal temperature, conduit fill, grounding, and overcurrent protection must be verified by a qualified professional.
Show solution steps See load conversion, voltage drop, ampacity, and selected cable reasoning
  1. Enter values to see the full solution steps and checks.

How to Use a Cable Sizing Calculator Correctly

A cable sizing calculator helps answer one practical question: what conductor size do I need for this load, voltage, cable length, and installation condition? The answer should not be based on current alone. A useful result checks both ampacity, which is the conductor’s current-carrying capacity, and voltage drop, which is the voltage lost over the cable run.

That is why this calculator is designed to show more than a single wire size. It estimates the recommended conductor, voltage drop in volts and percent, voltage at the load, adjusted ampacity, power loss, and the reason the size was selected. For final work, always verify the result against the adopted electrical code, equipment terminations, conductor insulation, raceway conditions, and local requirements.

Primary purpose Find a cable size that passes ampacity and voltage-drop checks
Most important inputs Amps, voltage, phase, one-way length, material, drop limit
Most useful outputs Recommended size, voltage drop, adjusted ampacity, governing check

Cable Sizing Formulas

Cable sizing usually starts with two checks. First, the conductor must carry the required design current after any derating. Second, the same conductor must keep voltage drop within the selected limit. A short run may be controlled by ampacity. A long run may require a larger conductor because voltage drop becomes the limiting factor.

DC and Single-Phase Voltage Drop

\[ V_d = 2 \cdot I \cdot R \cdot L \]

The factor of 2 accounts for the out-and-back current path. The calculator asks for one-way length and applies the return path internally.

Three-Phase Voltage Drop

\[ V_d = \sqrt{3} \cdot I \cdot R \cdot L \]

Three-phase circuits use the square-root-of-three relationship. This calculator uses a simplified resistance-only voltage-drop estimate and does not include AC reactance.

Voltage Drop Percentage

\[ \%V_d = \frac{V_d}{V_{system}} \times 100 \]

Voltage drop percent compares the lost voltage to the source voltage. This is especially important for low-voltage systems because a small loss in volts can be a large percentage loss.

Design Current and Ampacity Check

\[ I_{design} = I_{load} \cdot F_{load} \]
\[ I_{adjusted} = I_{base} \cdot F_{derating} \]

Voltage drop is normally checked using the actual load current. Ampacity is checked using design current after any continuous-load or project-specific factor.

Important calculation note

This calculator is an educational sizing tool. It uses built-in resistance and approximate ampacity data to estimate a practical conductor size. It does not replace final code review, equipment documentation, or a full engineered design.

Inputs That Change Cable Size the Most

The best cable sizing calculator should not overwhelm users with unnecessary fields, but it must include the inputs that actually change the result. The table below explains the main values users should understand before trusting the recommendation.

Main cable sizing inputs and why they matter
InputWhat to EnterHow It Changes the Result
Load CurrentThe actual operating current in ampsHigher current increases both voltage drop and ampacity demand
PowerWatts, kW, VA, kVA, or horsepower if current is unknownThe calculator converts power to current using voltage, phase, power factor, and efficiency
System VoltageNominal source voltage; line-to-line voltage for three-phaseLower voltage systems are more sensitive to voltage drop
One-Way LengthDistance from source to load, not the round-trip pathLonger runs often require larger conductors for voltage-drop control
Phase TypeDC, single-phase AC, or three-phase ACChanges the voltage-drop equation used by the calculator
Conductor MaterialCopper or aluminumAluminum usually needs a larger size than copper for the same voltage-drop target
Voltage-Drop LimitCommon targets include 2%, 3%, or 5%A tighter limit usually increases conductor size
Derating FactorAdjustment for installation conditionsLower derating factors reduce usable ampacity and may force a larger conductor
Parallel ConductorsNumber of parallel runs per phase or polaritySplits current between conductors and can reduce drop per run, but must be code-verified

Ampacity vs. Voltage Drop

The most important idea in cable sizing is that ampacity and voltage drop are not the same check. A conductor may be large enough to safely carry the current but still be too small for a long run because the voltage at the load becomes too low.

When Ampacity Governs

  • The load current is high relative to the conductor size
  • A continuous-load factor is applied
  • Temperature or conductor grouping reduces usable ampacity
  • The termination rating limits the usable ampacity basis

When Voltage Drop Governs

  • The cable run is long
  • The circuit is 12 V, 24 V, or another low-voltage system
  • The selected voltage-drop limit is tight
  • The load is sensitive to low delivered voltage

How to use the governing criterion

If the calculator says voltage drop controls, the conductor was likely upsized for performance over distance. If it says ampacity controls, the current-carrying requirement is the limiting check.

What Is an Acceptable Voltage Drop?

A common design target is about 3% for a branch circuit and about 5% total for feeder plus branch circuit voltage drop. These are commonly used educational design targets, not a substitute for the final requirements that apply to your specific installation.

1% to 2%

Useful for sensitive electronics, low-voltage controls, instrumentation, and performance-critical DC circuits.

3%

A common branch-circuit design target for keeping delivered voltage close to source voltage.

5%

A common overall feeder-plus-branch target when evaluating the full circuit path.

Voltage drop is especially important on 12 V and 24 V circuits. A 2 V drop is less than 1% on a 240 V circuit, but more than 16% on a 12 V circuit. That is why low-voltage DC cable sizing often requires much larger conductors than users expect.

AWG and mm² Cable Size Chart

Users often search for cable size in either AWG/kcmil or mm². These systems are not exact one-to-one matches, so the calculator should treat metric values as nearest standard sizes rather than perfect equivalents.

Common AWG sizes and approximate metric cross-sectional areas
AWG / kcmilApprox. AreaNearest Common Metric SizeTypical User Context
14 AWG2.08 mm²2.5 mm²Small branch circuits and light loads, subject to local code limits
12 AWG3.31 mm²4 mm²Common small branch circuit comparison size
10 AWG5.26 mm²6 mm²Higher current branch circuits and longer small-load runs
8 AWG8.37 mm²10 mm²Longer 30–50 A style runs, depending on conditions
6 AWG13.3 mm²16 mm²Feeders, EV-style loads, and longer circuits
4 AWG21.2 mm²25 mm²Larger feeders and voltage-drop-controlled designs
2 AWG33.6 mm²35 mm²Large branch circuits and feeder comparisons
1/0 AWG53.5 mm²70 mm²Larger feeders and service-style comparisons
4/0 AWG107.2 mm²120 mm²Large feeders where voltage drop and ampacity both matter
500 kcmil253 mm²300 mm²Large equipment feeders, often requiring full engineering review

Do not treat AWG and mm² as exact replacements

AWG and metric conductor sizes come from different sizing systems. When switching between them, use the next suitable standard size and verify final ampacity, voltage drop, insulation, and termination requirements.

Copper vs. Aluminum Cable Sizing

Copper and aluminum can both be valid conductor materials, but they do not size the same way. Copper has lower electrical resistance, so it usually meets the same voltage-drop target with a smaller conductor. Aluminum can still be economical for larger feeders, but it requires compatible terminations, connectors, torque requirements, and installation practices.

Copper vs. aluminum comparison for preliminary cable sizing
FactorCopperAluminum
ResistanceLowerHigher
Typical conductor size for same dropUsually smallerUsually larger
Common use caseBranch circuits, compact spaces, smaller equipment runsLarger feeders and cost-sensitive larger installations
Main cautionHigher material costRequires aluminum-rated terminations and correct installation practice

Important aluminum note

A calculator may show aluminum as a workable option, but the final installation must still confirm equipment lugs, connectors, torque values, conductor type, and local code requirements.

Single-Phase, Three-Phase, and DC Cable Sizing

The same current, voltage, and length can produce a different result depending on whether the system is DC, single-phase AC, or three-phase AC. This is why the calculator asks for circuit type before recommending a conductor.

DC Circuits

DC systems use an out-and-back conductor path. Low-voltage DC systems, such as 12 V and 24 V, are often voltage-drop controlled.

Single-Phase AC

Single-phase circuits also use a two-conductor voltage-drop path in this simplified calculator. Long runs can quickly require larger conductors.

Three-Phase AC

Three-phase voltage drop uses the square-root-of-three relationship. This is common for commercial, industrial, and larger equipment feeders.

Reactance Limitation

This calculator uses a resistance-only estimate. For large AC conductors, long motor feeders, or power-factor-sensitive designs, a full impedance-based calculation may be required.

Common Cable Sizing Use Cases

The same calculator can support many search intents, but users should interpret the result differently depending on the application. A cable size that is reasonable for a low-voltage control circuit may not be appropriate for building branch-circuit wiring.

Common cable sizing scenarios and what to pay attention to
Use CaseMost Important CheckPractical Warning
12 V / 24 V DCVoltage drop percentageEven small voltage losses can be severe at low voltage
120 V / 240 V branch circuitsAmpacity, voltage drop, and overcurrent protectionDo not use the calculator result as final code approval
480 V three-phase feedersAmpacity, voltage drop, and installation deratingLarge AC feeders may require impedance-based voltage drop
Solar / battery / inverter wiringVoltage drop and continuous currentDC current can be high, and conductor heating must be reviewed carefully
Motor circuitsStarting performance, voltage drop, and code-specific motor rulesMotor sizing may require dedicated rules beyond a simple calculator
EV charging circuitsContinuous load factor and ampacityLong-duration loading and equipment instructions matter

How to Use the Cable Sizing Calculator

Use the calculator like a structured design check. Start with the load, voltage, and one-way length. Then review whether the selected conductor passes both ampacity and voltage-drop limits.

1

Choose size mode or check mode

Use Size a new cable when you need a recommendation. Use Check an existing cable if you already have an AWG, kcmil, or mm² conductor size.

2

Enter current or power

If you know amps, enter current directly. If you know watts, kW, VA, kVA, or horsepower, choose the power input option so the calculator can estimate current first.

3

Enter one-way cable length

Do not double the cable length manually. Enter the one-way distance from source to load. The calculator applies the appropriate path relationship internally.

4

Select material and voltage-drop target

Choose copper or aluminum, then set the maximum voltage drop. For many preliminary branch-circuit checks, 3% is a common starting point.

5

Use Advanced Options when conditions are not standard

Set continuous-load factor, derating factor, conductor temperature, application type, and parallel conductors when those conditions affect the result.

Step-by-Step Worked Example

A worked example helps explain why the calculator may recommend a larger conductor than expected. In many real circuits, voltage drop rather than ampacity controls the final size.

Example Scenario

System
240 V single-phase AC
Load
48 A continuous
One-way length
150 ft
Material
Copper
Voltage-drop target
3%
Load factor
125%

Design Current

\[ I_{design} = 48 \times 1.25 = 60\text{ A} \]

Voltage-Drop Limit

\[ V_{d,max} = 240 \times 0.03 = 7.2\text{ V} \]

Interpretation

The calculator checks the conductor against the 60 A design current, but voltage drop is based on the actual 48 A load current. If a smaller conductor can carry the current but exceeds 7.2 V of drop, the calculator must size up for voltage performance.

What this example teaches

Cable sizing is not just about avoiding overheating. It is also about delivering enough voltage at the load. This is why long circuits, low-voltage systems, and sensitive equipment often require larger conductors.

How to Read the Calculator Results

The calculator output is designed to explain the recommendation, not just show a wire size. Use the table below to understand each result.

How to interpret the main cable sizing results
ResultWhat It MeansWhat to Check Next
Recommended cable sizeThe smallest built-in conductor that passes ampacity and voltage-drop checksVerify it against local code, equipment ratings, and installation method
Existing cable passes/failsWhether the cable you selected in check mode passes the calculator’s checksIf it fails, review whether ampacity or voltage drop caused the failure
Load currentThe current used for voltage-drop calculationConfirm the actual load estimate is realistic
Design currentThe current used for ampacity after load factorCheck whether a continuous-load factor or equipment-specific rule applies
Voltage dropEstimated volts and percent lost in the conductor runCompare against the selected maximum voltage-drop limit
Voltage at loadEstimated delivered voltage after conductor dropConfirm the load can operate properly at that voltage
Adjusted ampacityBase ampacity after derating and parallel-run adjustmentVerify final ampacity using the applicable code table and installation conditions
Power lossEstimated conductor loss as heatLarge losses may justify upsizing for efficiency

Temperature and Grouping Derating

Derating is one of the most important reasons a simple wire-size answer can be wrong. Conductors may need to be derated for ambient temperature, number of current-carrying conductors, raceway conditions, insulation type, and equipment terminations.

Why derating matters

A conductor that appears acceptable from a basic ampacity table may no longer pass once correction and adjustment factors are applied. When in doubt, use a conservative derating factor and verify the final value from the governing code.

Ambient Temperature

Higher ambient temperature can reduce conductor ampacity.

Conductor Grouping

Multiple current-carrying conductors in the same raceway can require ampacity adjustment.

Termination Temperature

Equipment terminals may limit the ampacity column that can be used.

Common Cable Sizing Mistakes That Cause Wrong Answers

These mistakes are common because cable sizing looks simple until installation conditions, voltage drop, and code limitations are included.

Common Don’ts

  • Size by ampacity only and ignore voltage drop
  • Enter round-trip length when the calculator asks for one-way length
  • Use copper results for aluminum conductors
  • Ignore continuous-load requirements
  • Assume AWG and mm² sizes are exact equivalents
  • Ignore temperature, grouping, raceway, and termination effects
  • Treat a preliminary calculator result as final code approval

Better Checks

  • Check both ampacity and voltage drop
  • Use one-way source-to-load length
  • Select the correct phase type
  • Use a realistic voltage-drop target
  • Review the nearby cable comparison table
  • Use advanced options when installation conditions are not standard
  • Verify final design against the adopted electrical code

When It Makes Sense to Size Up

The smallest passing conductor is not always the best practical choice. If the result is close to the voltage-drop limit or ampacity margin is thin, going one size larger can improve performance, reduce losses, and provide future flexibility.

Long Cable Runs

If voltage drop is close to the limit, upsizing may provide better end-of-line voltage and lower power loss.

Low-Voltage DC

12 V and 24 V circuits are often worth upsizing because small voltage losses become large percentage losses.

Motor or Compressor Loads

Reduced voltage can affect starting and performance, so additional voltage-drop margin may be useful.

Future Load Growth

A slightly larger conductor may avoid expensive rework if the equipment load increases later.

Limitations of This Cable Sizing Calculator

This calculator is intended for educational estimating and preliminary design review. It gives a strong starting point, but it does not model every condition that may govern final conductor selection.

Code Compliance

The calculator does not guarantee NEC, IEC, BS 7671, AS/NZS, or local-code compliance.

AC Reactance

Large AC conductors and long feeders may need impedance-based voltage-drop calculations.

Fault Current

Short-circuit withstand, fault loop impedance, and protective-device coordination are not fully modeled.

Installation Details

Conduit fill, insulation type, terminals, wet locations, burial conditions, and manufacturer requirements must be checked separately.

High-quality external references

For additional verification, compare the result against manufacturer and standards-based resources such as the Southwire Voltage Drop Calculator, the Encore Wire Size and Voltage Drop Calculator, or an IEC/BS-style cable sizing method when your project is outside a U.S. NEC-style context.

Frequently Asked Questions

What does a cable sizing calculator actually calculate?

It estimates the conductor size needed to satisfy current-carrying capacity and voltage-drop limits for the load, voltage, length, phase type, and conductor material you enter.

Is cable sizing based on amps or voltage drop?

It should be based on both. Ampacity checks whether the conductor can safely carry the design current, while voltage drop checks whether the load receives enough voltage over the run.

Do I enter one-way cable length or total round-trip length?

Enter one-way length from the source to the load. The calculator applies the correct voltage-drop path internally for DC, single-phase AC, or three-phase AC.

Why is my recommended cable size larger than expected?

The most common reasons are long distance, low system voltage, a tight voltage-drop limit, continuous-load adjustment, aluminum conductors, or derating for installation conditions.

Why does low-voltage DC often need larger cable?

Low-voltage systems are very sensitive to percentage voltage drop. A small loss in volts can be a large percentage of a 12 V or 24 V supply.

Should I use copper or aluminum cable?

Copper usually sizes smaller because it has lower resistance. Aluminum can be practical for larger feeders, but the final design must confirm compatible equipment terminations and installation requirements.

What does “governing criterion” mean?

It tells you whether the selected conductor size was controlled mainly by ampacity or by voltage drop. This explains why the calculator did not choose a smaller conductor.

Can I use this calculator for final electrical design?

Use it as a preliminary educational tool. Final design must be checked against the adopted electrical code, equipment manufacturer requirements, conductor insulation, temperature ratings, installation method, and local authority requirements.