Skip to the wire ampacity table

Interactive Electrical Engineering Reference

Wire Ampacity Chart

Look up copper and aluminum conductor ampacity by wire size, then select up to three rows to compare 60°C, 75°C, and 90°C values.

  • Base condition: 30°C ambient
  • Units: amperes
  • Materials: copper and aluminum
  • Use: preliminary reference

Interactive Wire Ampacity Table

Find a wire size: filter or search the table, then select up to three rows for the comparison chart below.

Educational ampacity reference based on commonly used NEC Table 310.16 values for not more than three current-carrying conductors in a raceway, cable, or earth at 30°C ambient. Final design remains subject to all applicable code rules and equipment limitations.
SelectAllowable ampacity by conductor temperature ratingAction
14 AWGCopper15 A20 A25 A
12 AWGCopper20 A25 A30 A
10 AWGCopper30 A35 A40 A
8 AWGCopper40 A50 A55 A
6 AWGCopper55 A65 A75 A
4 AWGCopper70 A85 A95 A
3 AWGCopper85 A100 A115 A
2 AWGCopper95 A115 A130 A
1 AWGCopper110 A130 A145 A
1/0 AWGCopper125 A150 A170 A
2/0 AWGCopper145 A175 A195 A
3/0 AWGCopper165 A200 A225 A
4/0 AWGCopper195 A230 A260 A
250 kcmilCopper215 A255 A290 A
300 kcmilCopper240 A285 A320 A
350 kcmilCopper260 A310 A350 A
400 kcmilCopper280 A335 A380 A
500 kcmilCopper320 A380 A430 A
600 kcmilCopper350 A420 A475 A
750 kcmilCopper400 A475 A535 A
1000 kcmilCopper455 A545 A615 A
12 AWGAluminum15 A20 A25 A
10 AWGAluminum25 A30 A35 A
8 AWGAluminum30 A40 A45 A
6 AWGAluminum40 A50 A55 A
4 AWGAluminum55 A65 A75 A
3 AWGAluminum65 A75 A85 A
2 AWGAluminum75 A90 A100 A
1 AWGAluminum85 A100 A115 A
1/0 AWGAluminum100 A120 A135 A
2/0 AWGAluminum115 A135 A150 A
3/0 AWGAluminum130 A155 A175 A
4/0 AWGAluminum150 A180 A205 A
250 kcmilAluminum170 A205 A230 A
300 kcmilAluminum195 A230 A260 A
350 kcmilAluminum210 A250 A280 A
400 kcmilAluminum225 A270 A305 A
500 kcmilAluminum260 A310 A350 A
600 kcmilAluminum285 A340 A385 A
750 kcmilAluminum320 A385 A435 A
1000 kcmilAluminum375 A445 A500 A

Important: These are base reference values, not automatic breaker sizes or final conductor selections. The 90°C column may be useful for correction and adjustment calculations when permitted, but lower terminal, equipment, conductor-protection, or application-specific limits may govern.

More filters and comparison options

Bulk CSV download is intentionally unavailable because NEC/NFPA table content is copyrighted. Use the copy-row action for a limited result summary and consult the official standard for authoritative project use.

Interactive comparison

Ampacity Comparison for Selected Conductors

Select up to three conductors in the table to compare their ampacity.

Optional chart controls

Refine the Comparison Chart

Table checkboxes are the primary selector. These dropdowns provide a faster alternative on small screens.

Changing these dropdowns updates the same selected rows and chart shown above.

Key Takeaways

  • Do not select the largest number: A 90°C insulation rating does not automatically make the 90°C table value the final allowable ampacity.
  • Apply both types of derating: Ambient-temperature correction and current-carrying-conductor adjustment address different thermal conditions.
  • Check the complete circuit: Ampacity, overcurrent protection, continuous load, equipment rules, and voltage drop are related but separate checks.
  • Confirm the adopted code: The applicable NEC edition and local amendments are determined by the jurisdiction and authority having jurisdiction.

Important Wire Ampacity Limitations

Do not use this chart as installation approval

This page is an educational conductor-ampacity reference. It does not verify the wiring method, equipment listing, terminal markings, conductor insulation, conductor-count exceptions, neutral treatment, rooftop conditions, cable-tray requirements, service-conductor rules, motor rules, HVAC rules, photovoltaic rules, flexible-cord requirements, parallel-conductor design, or local amendments for a specific installation.

Method and interpretation

How to Use the Wire Ampacity Chart

Follow the complete selection path instead of stopping at one table cell.

  1. Identify the correct conductor material and size. Copper and aluminum conductors have different allowable ampacities for the same designation.
  2. Select the applicable conductor temperature rating. The insulation type and code rules determine which temperature column may be used for calculations.
  3. Apply installation-condition factors. Correct for ambient temperature and adjust for the number of current-carrying conductors when required.
  4. Apply the lowest governing limitation. Compare the adjusted result with terminal ratings, equipment limitations, conductor-protection rules, and special application requirements.

Variables, Symbols, and Units

\(I_{\text{base}}\)
Base ampacity in amperes from the applicable conductor temperature column.
\(F_{\text{ambient}}\)
Ambient-temperature correction factor, expressed as a dimensionless multiplier.
\(F_{\text{conductors}}\)
Adjustment factor for the applicable number of current-carrying conductors.
\(I_{\text{adjusted}}\)
Calculated ampacity after the selected correction and adjustment factors.

Why the Temperature Columns Differ

The 60°C, 75°C, and 90°C columns represent conductor ampacities associated with different allowable conductor temperature ratings. A conductor may have 90°C-rated insulation while being connected to equipment with lower-rated terminals. In that case, the higher insulation rating can sometimes be used during correction or adjustment calculations, but the final permitted ampacity remains subject to the lower applicable terminal or equipment limitation.

60°C column

Commonly relevant where equipment terminals or conductor-use rules impose a 60°C limitation.

75°C column

Frequently used with equipment and conductors specifically identified for 75°C terminations.

90°C column

Often useful as the starting value for permitted correction and adjustment calculations, but not automatically the final circuit ampacity.

Ambient-Temperature Correction Factors Used by the Tool

The calculator uses temperature bands associated with 60°C, 75°C, and 90°C conductor ratings. It does not interpolate between bands or extrapolate outside the supported range.

Ambient-temperature correction factors applied by the interactive lookup.
Ambient temperature60°C conductor75°C conductor90°C conductor
10°C or less1.291.201.15
11–15°C1.221.151.12
16–20°C1.151.111.08
21–25°C1.081.051.04
26–30°C1.001.001.00
31–35°C0.910.940.96
36–40°C0.820.880.91
41–45°C0.710.820.87
46–50°C0.580.750.82
51–55°C0.410.670.76
56–60°C0.580.71
61–65°C0.470.65
66–70°C0.330.58
71–75°C0.50
76–80°C0.41

Current-Carrying-Conductor Adjustment Used by the Tool

Adjustment factors selected by the entered number of current-carrying conductors.
Current-carrying conductorsAdjustment factor
1–3100%
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 or more35%
Conductor-count caution

Do not assume every conductor in a raceway or cable is counted the same way. Equipment grounding conductors are not normally current carrying, and neutral-conductor treatment can depend on the circuit. Verify the applicable counting rules for the actual installation.

Worked ampacity examples

Wire Ampacity Calculation Examples

12 AWG Copper With 90°C Insulation and 60°C Terminations

Given: 12 AWG copper, 90°C insulation, 60°C terminations, 30°C ambient, and three current-carrying conductors.

Method: The 90°C base value is 30 A. Both correction factors equal 1.00, but the 60°C reference value is 20 A.

Result: The preliminary governing ampacity is 20 A because the lower termination limitation controls.

Check: Small-conductor overcurrent-protection rules and the actual equipment markings must still be verified.

6 AWG Copper in 40°C Ambient With Six Current-Carrying Conductors

Given: 6 AWG copper, 90°C insulation, 75°C terminations, 40°C ambient, and six current-carrying conductors.

Method: Start with 75 A from the 90°C column, multiply by 0.91 for ambient temperature and 0.80 for conductor count.

Result: Adjusted ampacity is \(75 \times 0.91 \times 0.80 = 54.6\text{ A}\).

Check: The adjusted value is below the 65 A value associated with the 75°C column, so the selected thermal adjustments govern this simplified example.

Engineering decision guide

What to Select, Check, and Avoid

Use this chart when

  • You need a quick copper or aluminum conductor ampacity lookup.
  • You want to compare 60°C, 75°C, and 90°C table columns.
  • You need a preliminary first-size check after basic derating.

Verify separately

  • Breaker or fuse selection and small-conductor protection rules.
  • Voltage drop, fault current, short-circuit withstand, and equipment instructions.
  • Special rules for motors, HVAC, EV charging, PV, services, feeders, welders, cable tray, flexible cords, and parallel conductors.

Common mistakes

  • Using the 90°C value as the final ampacity without checking terminals.
  • Confusing conduit fill with current-carrying-conductor adjustment.
  • Selecting a breaker directly from one ampacity table value.

Copper vs. Aluminum Wire Ampacity

Aluminum conductors generally require a larger conductor designation than copper to provide a comparable ampacity. Material selection also affects conductor size, weight, cost, termination requirements, equipment compatibility, installation practices, and oxidation-control requirements. The ampacity chart is therefore only one part of a material-selection decision.

Ampacity vs. Breaker Size vs. Voltage Drop

Ampacity
The conductor’s allowable current under defined thermal and installation conditions.
Breaker size
The overcurrent-protection rating selected under applicable load, equipment, conductor, and code rules.
Voltage drop
The reduction in voltage caused by conductor impedance over the circuit length.
Design current
The current that the conductor and protective system must serve after applicable load factors are considered.

When This Wire Ampacity Chart Does Not Apply

Another table or calculation method may be required for conductors in free air, flexible cords, service conductors, medium-voltage conductors, cable tray, rooftop raceways, direct sunlight, high-temperature equipment, parallel conductors, motors, generators, transformers, welders, HVAC equipment, electric-vehicle charging systems, photovoltaic systems, storage batteries, or manufacturer-controlled assemblies.

Wire Ampacity Chart Engineering References

NEC conductor ampacity reference · AWG, kcmil and amperes · Dataset version 1.0

The page uses a transformed educational presentation of conductor ampacity concepts and commonly referenced values. The official NFPA publication remains the controlling source for project-specific code work.

Dataset and Review Details

Edition or revision
2023 NEC educational basis; verify locally adopted edition
Method
Base ampacity × ambient factor × conductor-count factor, then governing-limit comparison
Scope
Copper and aluminum insulated conductors from common AWG through 1000 kcmil sizes
Known exclusions
Special applications, alternate wiring methods, local amendments, equipment-specific rules, and project approval
Last reviewed
Engineering reviewer
Turn2Engineering Editorial Team
Rights status
Limited educational transformation; no full NEC-derived CSV distribution
Dataset version
Wire Ampacity Reference 1.0

Frequently Asked Questions

The reference values for 12 AWG copper are 20 A at 60°C, 25 A at 75°C, and 30 A at 90°C, but that does not mean every 12 AWG installation may be used at those currents. Terminal ratings, small-conductor overcurrent-protection rules, wiring method, insulation, ambient temperature, conductor count, equipment rules, and local code determine the final permitted application.

The three values correspond to 60°C, 75°C, and 90°C conductor temperature ratings. The applicable value depends on conductor insulation, terminal ratings, equipment markings, conductor size, and code rules. The highest value is not automatically the allowable circuit ampacity.

A 90°C conductor rating may be used as the starting value for permitted correction and adjustment calculations, but the final ampacity remains limited by applicable terminal ratings, equipment instructions, conductor-protection rules, and other code requirements.

Yes. When ambient temperature exceeds the table’s reference condition, an applicable correction factor can reduce conductor ampacity. Additional adjustments may also be required for multiple current-carrying conductors or special installation conditions.

No. Ampacity is a conductor thermal limit under defined conditions. Breaker or fuse selection also depends on load characteristics, continuous operation, equipment requirements, conductor-protection rules, permitted standard ratings, and application-specific NEC provisions.

Wire Ampacity Chart Summary

Use the interactive chart to identify a base conductor ampacity, apply supported ambient-temperature and conductor-count factors, and see which selected limitation governs. The result is most useful as a transparent preliminary check because it shows the calculation path instead of returning one unexplained number.

Complete conductor design requires more than an ampacity table. After confirming the applicable code edition and installation method, check overcurrent protection, voltage drop, equipment instructions, special application rules, fault-current requirements, and local amendments.

Where to Go Next

Scroll to Top