HVAC CFM Calculator

Calculate HVAC airflow from room size, air changes, system capacity, duct velocity, sensible output, or known airflow.

Calculator is for informational purposes only. Terms and Conditions

\[ CFM=\frac{LWH\cdot ACH}{60} \]
1

Choose the calculation setup

Select the method that matches the HVAC information you already know.

Choose the method based on whether you know room size, cooling capacity, duct velocity, sensible output and temperatures, or existing airflow.
Changing the preset converts entered values so their physical quantities remain unchanged.
A selected space type inserts an editable planning ACH value. It is not a code-required outdoor-air rate.
Example values are prefilled. Replace them with your room dimensions and intended air-change rate.
2

Enter the known values

Only inputs required by the active method are displayed and enabled.

Enter the inside length of the conditioned room or space.
Enter the inside width of the conditioned room or space.
Use the average clear ceiling height for a sloped or irregular room.
This editable planning value represents total room air changes, not automatically code-required outdoor ventilation.
Advanced Options
3

Airflow Visual

The diagram updates with the active method, inputs, and calculated result.

HVAC CFM calculation diagram A live technical diagram showing the selected HVAC airflow calculation inputs and result.
4

Solution

Live result, practical checks, warnings, and calculation steps.

Required HVAC Airflow
Enter the required values to calculate.

Quick checks

  • Quick check
Show solution steps Review conversions, equations, substitutions, assumptions, and result
  1. Enter valid values to see the complete solution.
5

Source, Standards, References, and Assumptions

Calculation basis, authoritative references, limitations, and verification requirements.

Standard HVAC airflow equations

The active method uses standard airflow, air-change, duct-area, capacity, or sensible-heat relationships and does not independently establish code compliance or installed-system performance.

References
  • Enter valid values to see assumptions and limitations for the selected method.

Calculator Guide

How to Use the HVAC CFM Calculator

The HVAC CFM Calculator above calculates room airflow from room size and air changes, whole-system airflow from cooling capacity, airflow through round or rectangular ducts, estimated airflow from sensible output and measured temperatures, or air changes per hour from known airflow. CFM means cubic feet per minute, a volumetric airflow rate describing how much air passes a location each minute. Select the method that matches the information you know, enter measured or documented values, and choose the desired output units.

Each calculation method answers a different HVAC question. An ACH calculation estimates theoretical room-air exchange, while a capacity-based calculation estimates an equipment airflow target. Duct airflow depends on clear area and average velocity, and the sensible-output method estimates operating airflow from heat transfer. Use the result only for the purpose represented by the selected method.

Best for Room airflow, equipment targets, duct CFM, operating airflow estimates, and ACH checks
Main result Airflow in CFM, m³/h, L/s, or m³/s, or air changes per hour
Most influential input The selected ACH, airflow per capacity, duct velocity, or supply-to-return temperature difference

Quick Answer

For room CFM, calculate room volume, multiply by ACH, and divide by 60. For system airflow, multiply cooling capacity by the selected airflow target. For duct CFM, multiply clear cross-sectional area by average velocity.

Total HVAC airflow is not automatically outdoor ventilation

Supply air can include mostly recirculated air. An ACH or CFM result does not by itself establish the outdoor-air rate, exhaust requirement, heating or cooling load, equipment compatibility, duct-system performance, or compliance with an adopted standard or code.

Which HVAC CFM Calculation Method Should You Use?

Choose the method according to the physical information you know and the decision you need to make. Using the wrong method can produce a mathematically correct answer that does not represent the airflow needed for the application.

HVAC CFM calculation methods and appropriate uses
Information availableCalculator methodResult meaningPrimary limitation
Room dimensions and an ACH targetRoom CFM from room size and ACHAirflow required to produce the selected theoretical room-air exchange rateDoes not calculate room heating or cooling demand
Cooling capacity and airflow per unit capacitySystem CFM from cooling capacityPreliminary whole-system airflow targetActual blower airflow depends on equipment data and static pressure
Duct dimensions and average velocityCFM through a ductVolumetric airflow through the measured duct sectionVelocity must represent the cross-sectional average
Sensible output plus supply and return temperaturesCFM from capacity and temperaturesEstimated operating airflow carrying the sensible heat rateDepends on correct output capacity, representative temperatures, and air properties
Known room airflow and room dimensionsACH from known airflowTheoretical room-volume air changes per hourDoes not measure outdoor-air fraction or mixing effectiveness
Method-selection rule: Use ACH for room-air-exchange planning, capacity-based airflow for equipment targets, area times velocity for duct flow, and the sensible-heat method for an operating airflow estimate.

HVAC CFM Calculator Inputs and Outputs

The visible inputs change with the selected method. Reliable results require measurements or documented equipment values that match the physical quantity requested by each field.

Room length, width, and ceiling height
These dimensions define effective room volume. Use clear inside dimensions. For sloped ceilings, use a representative average height rather than the maximum height.
Target air changes per hour
ACH is the number of theoretical room-volume air changes each hour. Space-type selections insert broad, editable circulation examples, not universal requirements.
Cooling system capacity
Enter nominal cooling capacity in refrigeration tons or kilowatts. Capacity is multiplied by the selected airflow intensity to estimate a system airflow target.
Airflow target per capacity
Use CFM per ton or L/s per kW from equipment data or a defensible design assumption. Approximately 400 CFM per ton is a common reference, not a universal requirement.
Duct shape and clear dimensions
Use the inside diameter for round ducts or the inside width and height for rectangular ducts. External sheet-metal dimensions may overstate clear flow area.
Average duct velocity
Enter the area-weighted average velocity across the duct. A single reading or grille face velocity may not represent actual duct CFM.
Sensible output capacity
Use sensible heat added to or removed from the airstream. Do not enter furnace input or total cooling capacity unless it has been converted to sensible output.
Return-air and supply-air temperatures
The calculator uses the absolute dry-bulb temperature difference. Measure representative mixed return air and delivered supply air under stable operation.
Known airflow
Use measured or rated airflow that actually enters the room when calculating ACH. Do not assign the entire air-handler airflow to one room unless the whole system serves only that room.
Calculated result
The primary output is airflow in CFM, m³/h, L/s, or m³/s. The reverse room method reports ACH and the approximate number of minutes per theoretical air change.

HVAC CFM Formulas

The calculator uses several established airflow relationships. Each formula has its own required units, assumptions, and appropriate application.

Room CFM from ACH

\[ CFM=\frac{LWH\left(ACH\right)}{60} \]

Use \(L\), \(W\), and \(H\) in feet. The product \(LWH\) is room volume in cubic feet, and dividing by 60 converts cubic feet per hour to cubic feet per minute.

Metric room airflow

\[ Q=\frac{V\left(ACH\right)}{3600} \]

Use room volume \(V\) in cubic metres to calculate airflow \(Q\) in m³/s. The factor 3,600 converts hours to seconds.

System airflow from cooling capacity

\[ CFM=\text{Cooling tons}\times\frac{CFM}{\text{ton}} \]

This gives a preliminary equipment airflow target based on the selected airflow intensity. It does not calculate the installed blower operating point.

Duct airflow from area and velocity

\[ Q=AV \]

In U.S. units, \(CFM=A_{\text{ft}^2}V_{\text{FPM}}\). In SI units, area in m² multiplied by velocity in m/s gives m³/s.

Round and rectangular duct area

\[ A_{\text{round}}=\frac{\pi D^2}{4} \qquad A_{\text{rectangular}}=WH \]

Use clear inside dimensions and convert them to the length units required by the airflow equation before calculating area.

Airflow from sensible output in U.S. units

\[ CFM\approx\frac{q_s}{1.08\left|T_s-T_r\right|} \]

Use sensible output \(q_s\) in Btu/h and dry-bulb temperature difference in °F. The coefficient 1.08 is a common standard-air approximation and may require correction for actual air density and conditions.

Airflow from sensible output in SI units

\[ Q\approx\frac{q_s}{1200\left|T_s-T_r\right|} \]

Use sensible output in watts and temperature difference in kelvins or degrees Celsius. The result is approximately m³/s under the assumed standard-air volumetric heat-capacity factor.

ACH from known CFM

\[ ACH=\frac{60\left(CFM\right)}{LWH} \]

Use room dimensions in feet. The formula calculates theoretical total room-volume exchanges per hour.

\(CFM\)
Volumetric airflow in cubic feet per minute.
\(Q\)
Volumetric airflow in a consistent unit such as m³/s.
\(L,W,H\)
Room or rectangular duct dimensions.
\(V\)
Room volume in the ACH formula or average air velocity in the duct formula, depending on context.
\(ACH\)
Air changes per hour.
\(A\)
Clear duct cross-sectional area.
\(D\)
Round duct inside diameter.
\(q_s\)
Sensible heating or cooling output delivered to the airstream.
\(T_s,T_r\)
Supply-air and return-air dry-bulb temperatures.

ACH is not a room load calculation

The room ACH formula estimates air exchange from an assumed rate. It does not determine the airflow required to offset heat gain or heat loss unless the selected ACH happens to produce the same airflow as a load-based calculation. To determine heating or cooling supply airflow, calculate the room sensible load and evaluate the required airflow at the available supply-to-room temperature difference.

How to Calculate HVAC CFM

Select the method first, then enter values that directly correspond to the requested physical quantities. Review the quick checks before using the main result.

Select what you want to calculate

Choose room airflow, system airflow, duct airflow, airflow from sensible output and temperatures, or ACH from known airflow. The calculator displays only the fields needed for that method.

Select the unit preset

Use HVAC industry units, U.S. customary units, or SI/metric units. Changing units converts existing values instead of reinterpreting the same number.

Enter measured or documented values

Use clear room and duct dimensions, average duct velocity, documented capacity, sensible output, and representative temperatures. Avoid guessed values when the result will support equipment or duct decisions.

Review the quick checks and warnings

Check room volume, air-change interval, equivalent unit conversions, CFM per capacity, duct area, velocity context, temperature difference, and warnings about unusual values.

Confirm what the result can establish

Use the result as an airflow estimate or target. Final design may still require load calculations, blower tables, static-pressure measurements, full duct design, terminal selection, ventilation calculations, and testing and balancing.

HVAC Airflow Input Checklist

Check the source and meaning of each input before relying on the calculated airflow.

  • Measure room length, width, and average ceiling height using consistent inside dimensions.
  • Treat space-type ACH values as editable planning examples rather than required ventilation rates.
  • Use equipment capacity in the unit shown by the selected field.
  • Use an airflow-per-capacity value supported by the equipment or a clearly stated preliminary assumption.
  • Measure clear inside duct dimensions rather than nominal exterior dimensions.
  • Use an area-weighted average duct velocity or a recognized traverse method.
  • Enter furnace output rather than input when using a heating sensible-output calculation.
  • Enter sensible cooling capacity rather than total cooling capacity in the dry-bulb sensible-heat equation.
  • Measure supply and return temperatures at representative locations after the system reaches stable operation.
  • Use room-specific airflow when calculating room ACH.

How to Interpret HVAC CFM Results

First identify whether the result is a theoretical room-air-exchange flow, a preliminary equipment target, a duct-section calculation, or an operating airflow estimate.

What the result means

CFM is a volumetric flow rate. It describes how much air moves each minute, not whether the air is properly distributed, conditioned, filtered, balanced, quiet, or code compliant.

What changes it most

Room airflow changes directly with volume and ACH. Duct airflow changes directly with area and velocity. Sensible-output airflow changes directly with capacity and inversely with temperature difference.

Fast sanity check

A 10% increase in ACH, room volume, duct area, velocity, capacity, or airflow intensity produces approximately a 10% increase in the associated airflow result.

Design airflow versus measured airflow

What different HVAC airflow results represent
Result sourceWhat it representsHow to use it
Room ACH calculationTheoretical room-air-exchange airflowVentilation planning, circulation comparison, or exhaust estimates
CFM per capacityPreliminary equipment airflow targetBlower or coil airflow comparison
Duct area × velocityCalculated flow through one duct sectionField verification when average velocity is reliable
Sensible-output methodEstimated operating airflowDiagnostic check when output and representative temperatures are known
Flow hood or duct traverseField-measured airflowTesting, balancing, commissioning, or troubleshooting

Suspicious result patterns

  • A normal room producing tens of thousands of CFM usually indicates a dimension, unit, or ACH error.
  • Duct CFM far above total blower airflow may indicate nominal grille area, incorrect diameter conversion, or an unrepresentative velocity reading.
  • An extremely high sensible-output airflow often results from an unrealistically small temperature difference or an incorrect capacity input.
  • Zero or negative dimensions, airflow, velocity, capacity, or ACH are not physically usable for these methods.
  • An unexpectedly high room ACH may mean total system airflow was assigned to a single room.

What to do next

Once design airflow is known, evaluate the duct path, register or diffuser, return path, pressure loss, blower operating point, and room load. If actual airflow is being checked, compare more than one measurement method when practical.

Worked Example: Room CFM from ACH

A room is 15 feet long, 12 feet wide, and 9 feet high. The selected planning rate is 6 air changes per hour.

Given values

Room length
\(L=15\text{ ft}\)
Room width
\(W=12\text{ ft}\)
Ceiling height
\(H=9\text{ ft}\)
Air-change rate
\(ACH=6\text{ h}^{-1}\)
Find
Required room airflow in CFM

Calculate room volume

\[ V=LWH=(15)(12)(9)=1620\text{ ft}^3 \]

Apply the formula

\[ CFM=\frac{V\left(ACH\right)}{60} \]

Substitute the values

\[ CFM=\frac{(1620)(6)}{60}=162\text{ CFM} \]

Result

Required room airflow \(\approx162\text{ CFM}\)

Under the simplified well-mixed-room assumption, this airflow produces six theoretical room-volume air changes each hour.

Verification check

Reverse the equation: \(ACH=60(162)/1620=6\). The original air-change target is recovered.

A second check is time per air change: \(60/6=10\) minutes. At 162 CFM, the system moves \(162\times10=1620\text{ ft}^3\), equal to the room volume.

Worked Example: HVAC System CFM from Cooling Capacity

A nominal 3-ton cooling system is evaluated using a preliminary airflow target of 400 CFM per ton.

Given values

Cooling capacity
\(3\text{ tons}\)
Airflow target
\(400\text{ CFM/ton}\)
Find
Preliminary equipment airflow target

Formula

\[ CFM=\text{Cooling tons}\times\frac{CFM}{\text{ton}} \]

Substitution

\[ CFM=(3)(400)=1200\text{ CFM} \]

Metric cross-check

\[ 3\text{ tons}\approx10.55\text{ kW} \]
\[ 400\text{ CFM/ton}\approx53.7\text{ L/s per kW} \]
\[ Q\approx(10.55)(53.7)=566\text{ L/s}\approx1200\text{ CFM} \]

Result

Preliminary equipment airflow target \(\approx1200\text{ CFM}\)

This is a comparison target, not proof that the installed blower delivers 1,200 CFM at the actual system static pressure.

Verification check

Dividing the result by capacity returns the selected airflow intensity: \(1200/3=400\text{ CFM/ton}\).

The metric calculation produces approximately 566 L/s, which converts back to approximately 1,200 CFM.

How Many CFM per Ton Does an HVAC System Need?

Approximately 400 CFM per ton is a common residential reference, but the correct airflow depends on the specific coil, blower, operating mode, sensible and latent loads, humidity objective, and manufacturer limits.

Common comparison values for system airflow
Cooling capacity350 CFM/ton400 CFM/ton450 CFM/ton
1.5 tons525 CFM600 CFM675 CFM
2 tons700 CFM800 CFM900 CFM
2.5 tons875 CFM1,000 CFM1,125 CFM
3 tons1,050 CFM1,200 CFM1,350 CFM
4 tons1,400 CFM1,600 CFM1,800 CFM
5 tons1,750 CFM2,000 CFM2,250 CFM

Lower airflow per ton

Lower airflow may increase moisture removal in some cooling applications, but excessive reduction can reduce capacity, increase temperature difference, and move the coil outside its intended operating range.

Higher airflow per ton

Higher airflow may increase sensible performance, but excessive airflow can reduce dehumidification, increase duct velocity and noise, and exceed blower or coil limits.

Reference context: Manufacturer educational guidance commonly describes approximately 400 CFM per ton as a general rule of thumb. Final airflow should come from equipment performance data and be verified at the installed operating point.

Worked Example: CFM Through a Round Duct

An 8-inch round duct has an average measured air velocity of 800 feet per minute.

Given values

Duct diameter
\(D=8\text{ in}\)
Average velocity
\(V=800\text{ FPM}\)
Find
Duct airflow in CFM

Convert diameter to feet

\[ D=\frac{8}{12}=0.6667\text{ ft} \]

Calculate duct area

\[ A=\frac{\pi D^2}{4} =\frac{\pi(0.6667)^2}{4} \approx0.349\text{ ft}^2 \]

Calculate airflow

\[ CFM=AV=(0.349)(800)\approx279\text{ CFM} \]

Result

Duct airflow \(\approx279\text{ CFM}\)

The result assumes 800 FPM is representative of average velocity across the entire clear circular area.

Verification check

Dividing airflow by area returns the original velocity: \(279/0.349\approx800\text{ FPM}\).

This equation calculates flow through a known section. It does not determine whether the duct is correctly sized for noise, friction, fittings, leakage, or available static pressure.

Worked Example: CFM from Sensible Output and Temperature Difference

An HVAC system provides 36,000 Btu/h of sensible output with a measured 20°F supply-to-return dry-bulb temperature difference.

Given values

Sensible output
\(q_s=36{,}000\text{ Btu/h}\)
Temperature difference
\(\Delta T=20^\circ\text{F}\)
Find
Estimated airflow in CFM

Formula

\[ CFM\approx\frac{q_s}{1.08\Delta T} \]

Substitution

\[ CFM\approx\frac{36{,}000}{(1.08)(20)} \approx1667\text{ CFM} \]

Result

Estimated airflow \(\approx1667\text{ CFM}\)

This result requires 36,000 Btu/h of sensible output. Furnace input or total cooling capacity cannot be substituted directly unless converted to the required sensible output.

Verification check

Multiply the estimated airflow by the heat-transfer coefficient and temperature difference: \(1.08(1667)(20)\approx36{,}007\text{ Btu/h}\), which agrees with the entered sensible output after rounding.

The result is an estimate because the 1.08 coefficient assumes approximate standard-air properties.

How to Use the Room-Type ACH Selections

The room-type selections are broad circulation-planning examples that automatically fill an editable ACH value. They are not required air-change rates and should not be presented as code values.

Use them for comparison

Space-type selections are useful for understanding how a lower or higher assumed ACH affects CFM for the same room volume.

Replace them when criteria are known

Use a project-specific ACH, outdoor-air rate, exhaust requirement, contaminant-control criterion, or load-based airflow when one has been established.

Do not treat them as outdoor air

Total room-air exchange can include recirculated supply air. Outdoor ventilation is a separate quantity.

Avoid specialized-space assumptions

Healthcare, laboratory, cleanroom, hazardous exhaust, commercial cooking, and industrial process spaces require application-specific criteria.

Ventilation context: ASHRAE identifies Standards 62.1 and 62.2 as standards for ventilation-system design and acceptable indoor air quality. Their requirements should not be replaced by a generic total-air ACH preset.

HVAC CFM Unit Conversions and Common Mistakes

Most large calculation errors come from mixing time bases, using the wrong area, confusing output with input capacity, or selecting a formula that does not match the intended airflow.

Do

  • Convert duct dimensions from inches to feet before calculating square feet.
  • Use diameter in \(A=\pi D^2/4\) or radius in \(A=\pi r^2\), but do not mix the two forms.
  • Use the factor 60 when converting between CFM and hourly room-air exchange.
  • Use an absolute temperature difference rather than an absolute temperature.
  • Use furnace output and sensible cooling output in the sensible-heat method.
  • Use a representative duct velocity average rather than one convenient point.

Don’t

  • Do not use square footage alone when ceiling height materially changes room volume.
  • Do not assume an ACH result is automatically the room heating or cooling airflow.
  • Do not treat 400 CFM per ton as mandatory for every system.
  • Do not multiply grille face velocity by nominal grille area without accounting for effective free area.
  • Do not use total cooling capacity in a sensible-only formula without separating the sensible portion.
  • Do not size a complete duct system from area and velocity alone.

Temperature difference conversion

A 20°F temperature difference equals approximately 11.1 K. Temperature differences use a scale ratio only; the 32-degree offset used for absolute temperatures does not apply.

Airflow conversion

One CFM is approximately 0.4719 L/s. Converting the output unit should change the displayed number without changing the physical airflow.

Why Calculated and Measured HVAC CFM Can Differ

A calculator produces a theoretical value, target, or estimate. Installed airflow is determined by the interaction of the blower, equipment components, duct system, controls, and field conditions.

Measured airflow is low

Check filters, coils, return restrictions, closed dampers, crushed flex duct, excessive fitting losses, duct leakage, zoning position, blower setup, and total external static pressure.

Measured airflow is high

Check fan programming, blower speed, bypass paths, duct velocity, terminal noise, equipment airflow limits, and whether the measurement correction or free area is correct.

Register totals do not match blower airflow

Leakage, inaccessible outlets, transfer paths, hood setup, terminal type, measurement tolerance, and system pressure changes can prevent register readings from summing exactly to blower airflow.

Temperature-based airflow looks unreasonable

Verify sensible output, measurement locations, stable operation, duct heat gain or loss, fan heat, air mixing, elevation, and whether total rather than sensible capacity was entered.

Common airflow measurement methods

  • Flow hood or balometer measurements at supply and return terminals.
  • Pitot-tube, hot-wire, or vane traverses across a suitable duct section.
  • Total external static pressure compared with manufacturer blower-performance tables.
  • Furnace output and temperature-rise airflow estimates.
  • Sensible cooling output and representative entering and leaving air temperatures.

HVAC CFM Calculator Assumptions and Limitations

The calculations are appropriate for education, preliminary estimates, comparison, and troubleshooting. They do not verify the complete HVAC design or installed system.

Uniform room mixing

ACH calculations assume airflow mixes through the entire effective room volume. Stratification, short-circuiting, dead zones, and diffuser placement can change actual performance.

Representative velocity

Duct airflow assumes the entered velocity represents the cross-sectional average. Real velocity profiles vary because of fittings, elbows, dampers, transitions, and measurement location.

Standard-air heat coefficients

The sensible-output method uses approximate standard-air coefficients. Elevation, pressure, temperature, and moisture content can affect air density and heat capacity.

No complete duct-system solution

Duct area and velocity do not establish effective length, fitting losses, leakage, friction rate, available static pressure, fan curve, balancing, or acoustics.

No equipment compatibility check

Capacity-based airflow does not verify blower capability, coil limits, moisture removal, furnace temperature rise, freeze protection, controls, or warranty requirements.

No code-compliance determination

The calculator does not establish compliance with ventilation, mechanical, energy, fire, healthcare, laboratory, environmental, or local requirements.

Final design and field verification

Final work may require heating and cooling load calculations, equipment selection using manufacturer performance data, complete duct design, terminal selection, outdoor-air and exhaust calculations, static-pressure testing, commissioning, and testing and balancing. The need for deeper review depends on the building, equipment, occupancy, contaminants, climate, and consequences of an incorrect result.

Related HVAC Calculators

Use the calculated airflow as an input to the next part of the HVAC workflow, or evaluate the air properties that affect sensible and latent performance.

Technical Sources

These sources support the ventilation distinction, residential duct-design limitations, and common CFM-per-ton reference discussed above.

HVAC CFM Calculator FAQ

These answers address the most common questions about system, duct, room, and measured HVAC airflow.

How many CFM does a 3-ton HVAC system need?

At 400 CFM per ton, a 3-ton system has a preliminary target of approximately 1,200 CFM. At 350 or 450 CFM per ton, the comparison values are 1,050 and 1,350 CFM. Confirm the correct range using the specific equipment data.

Is 400 CFM per ton always correct?

No. It is a common reference rather than a universal requirement. Coil design, climate, sensible and latent loads, humidity control, heating mode, blower capability, static pressure, and manufacturer limits can require a different airflow.

How much CFM can an 8-inch duct carry?

Airflow depends on velocity. An 8-inch round duct has an area of approximately 0.349 ft². At 600 FPM it carries about 209 CFM; at 800 FPM it carries about 279 CFM; at 1,000 FPM it carries about 349 CFM. Noise, friction, application, and system pressure still matter.

Is supply CFM the same as outdoor-air CFM?

No. Total supply airflow can contain mostly recirculated air. Outdoor-air CFM is the portion intentionally brought into the building. Exhaust, makeup air, transfer air, occupancy, floor area, and ventilation effectiveness may also affect outdoor-air design.

How much CFM should come from each supply register?

A simple starting allocation is room design CFM divided by the number of supply outlets. Final outlet count and selection must also consider throw, spread, terminal velocity, noise, pressure drop, ceiling height, room geometry, exterior load, and manufacturer performance data.

Can this calculator replace Manual J or Manual D?

No. The calculator evaluates individual airflow relationships. A complete residential design may require load calculation, equipment selection, duct-system design, terminal selection, manufacturer performance data, and field testing.

Scroll to Top